Crowcon Gasflag Installation, Operating And Maintenance Instructions For The Installer And The User

Crowcon Gasflag Installation, Operating And Maintenance Instructions For The Installer And The User

Single channel control panel alarm only apparatus

Advertisement

Quick Links

Gasflag
Single Channel Control Panel
Alarm Only Apparatus
Installation, operating and
maintenance instructions, M07225
Issue 2 1/07/05
Crowcon Detection Instruments Ltd
2 Blacklands Way
Abingdon Business Park
Abingdon OXON
OX14 1DY

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Gasflag and is the answer not in the manual?

Questions and answers

Summary of Contents for Crowcon Gasflag

  • Page 1 Gasflag Single Channel Control Panel Alarm Only Apparatus Installation, operating and maintenance instructions, M07225 Issue 2 1/07/05 Crowcon Detection Instruments Ltd 2 Blacklands Way Abingdon Business Park Abingdon OXON OX14 1DY...
  • Page 2 All connections and earth settings are clearly labeled on the PCB. The Gasflag is supplied with a 50/60 Hz ac power supply unit of 230 V input (E01777) and 110 V input (E01782). The power supplies have red and black terminals for connecting to the Gasflag and provide 13 to 28 V dc supply.
  • Page 3 The power supply provided with the Gasflag control unit is not fitted with an AC plug. As Gasflag is a safety device, the power supply must be permanently wired to a dedicated AC spur fed from a circuit breaker, marked as the disconnecting device for the Gasflag.
  • Page 4 A FALLING alarm is typically used to monitor oxygen levels as a fall in the oxygen level is most critical. LINKS 15 and 17 set the Gasflag configuration for ALARM 1 and 2. The links should be set to A for FALLING or B for RISING.
  • Page 5 LINKS 16 and 18 set the Gasflag configuration for ALARM 1 and 2, the links should be set to A for NON-LATCHING or B for LATCHING.
  • Page 6 Figure 3.1 Electrical connections for powering an external alarm device 3.4 Setting earthing requirements The Gasflag control panel provides flexible earthing arrangements. The LINKS 1 and 2 on the RELAY PCB allows earthing configuration for 0 V and SCREEN. The links are summarised in the table below.
  • Page 7 23.5 mA. 4.1 Fault condition If the Gasflag senses a fault from a short or open circuit condition the Fault Relay will change state, the Fault LED will illuminate and the BUZZER will sound a 1 Hz bleep. The fault alarm is non-latching and will return to normal if the fault condition clears.
  • Page 8 The Gasflag is supplied with a power supply unit capable of powering up to two Gasflag units. If more then two units are to be daisy chained together then a higher rated power supply is needed. In the "Figure 5.1"...