Additional Information required for CytroPac UL-Certification
A)
THE INTEGRAL DRIVE SOLID STATE SHORT CIRCUIT PROTECTION IN THESE UNITS
DOES NOT PRIVIDE BRANCH CIRCUIT PROTECTION. BRANCH CIRCUIT PROTECTION
MUST BE PROVIDED EXTERNALLY IN AACCORDANCE WITH THE MANUFACTURER'S
INSTRUCTIONS, NATIONAL ELECTRICAL CODE OR THE CANADIAN ELECTRICAL CODE,
PART I AS APPLICABLE, AND ANY ADDITIONAL LOCAL CODES.
B)
TRANSIENT SURGE SUPPRESSION SHALL BE INSTALLED ON THE LINE SIDE OF THIS
EQUIPMENT AND SHALL BE RATED 480V (PHASE TO GROUND), 480 V (PHASE TO
PHASE), SUITABLE FOR OVERVOLTAGE CATEGORY III, AND SHALL PROVIDE
PROTECTION FOR A RATED IMPULSE WITHSTAND VOLTAGE PEAK OF 6kV.
C)
SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE THAN 5,000
AMPERES, 480 VOLTS AC MAXIMUM, WHEN PROTECTED BY LISTED (JDDZ/7) CLASS J
FUSES.
DRIVE MODEL INCLUDED IN CYTROPAC:
EFC5610-1K50-3P4-M..
EFC5610-2K20-3P4-M..
EFC5610-3K00-3P4-M..
EFC5610-4K00-3P4-M..
D)
EXTERNAL CONTROL CIRCUIT OVERCURRENT PROTECTION SHALL BE PROVIDED IN
THE END USE, MAX. 1A. USE UL LISTED OR UL RECOGNIZED OVERCURRENT
PROTECTIVE DEVICES SUITABLE FOR INDUSTRIAL APPLICATIONS.
E)
FOR USE IN POLLUTION DEGREE 3 AND OVERVOLTAGE CATEGORY III IN ORDINARY
LOCATION ENVIRONMENTS ONLY.
Bosch Rexroth AG, Edition 07.2022, RE 51055-B
17�4 Additional document for UL listing
The additional document for UL listing is only relevant for CytroPac
according to type code CytroPac-1X/.../UL
FUSE CURRENT RATING:
10 A/ 600 V
15 A/ 600 V
20 A/ 600 V
20 A/ 600 V