UNINTERRUPTIBLE POWER SYSTEM
SERVICE MANUAL
Smartbitt SBOL50KTIII-3, SBOL60KTIII-3,
SBOL90KTIII-3 Tower Model

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SBOL50KTIII-3 and is the answer not in the manual?

Questions and answers

Summary of Contents for Smartbitt SBOL50KTIII-3

  • Page 1 UNINTERRUPTIBLE POWER SYSTEM SERVICE MANUAL Smartbitt SBOL50KTIII-3, SBOL60KTIII-3, SBOL90KTIII-3 Tower Model...
  • Page 3: General Information

    1. General Information 1.1 Getting start Ⅲ 30K(L)~200K(L) This manual is for Smartbitt tower UPS. It can help service person perform the basic maintenance and repair service. This manual only focuses on the service section, so you should get the basic operation of the UPS from the user manual, and make sure you had read and understood the user manual before reading the manual.
  • Page 4: Electric Specifications

    2. Electric Specifications CAPACITY* 30KVA/30KW 60KVA/60KW 100KVA/100KW 120KVA/120KW 180KVA/180KW 200KVA/200KW INPUT 110 VAC(L-N) ± 3 % at 50% Load Low Line Loss 176 VAC(L-N) ± 3 % at 100% Load Low Line Comeback Low Line Loss Voltage + 10V Voltage Range 300 VAC(L-N) ±...
  • Page 5: Functional Block

    3. Functional Block As a true online UPS, the product applies a double conversion topology, comprising functional blocks as shown in Figure 3.1 Single_Input System Principle Diagram Maintenance Bypass Bypass Byp SCR Input Output Input EMI Line SCR Output EMI Input OVCD relay Maintenance Bypass...
  • Page 6 The SPS generates DC power supply needed by operation of the circuit of the UPS itself. The Bypass provides a path that utility can power the output directly when the Inverter is not executed. Maintenance Bypass provides another path that utility can power the output directly when UPS is in maintenance status.
  • Page 7: Working Principle Of The Major Functional Block

    4. Working Principle of the Major Functional Block 4.1 Switch Power Supply The Switch Power Supply (SPS) supplies DC power for UPS operation. The input source of the SPS is the battery, or the output of the charger. SPS_BUS+ R LINE +12V Output S LINE Battery...
  • Page 8 4.2 PFC/Booster BUS+ Battery R/S/T BUS- Figure 4.2 PFC/Booster As shown in the Figure 4.2, when Q1/Q2 is on and D1/D2 is off, the current will increase to store energy in choke(L1/L2). When the Q1/Q2 is off and D1/D2 is on, the choke will release energy. Therefore, we can control the current in chokes (input current) by regulating the time of Q1/Q2 on and off.
  • Page 9: Emi Board

    4.4 Charger The function of charger is to charge and maintain the batteries at fully charged condition. The charger charges the batteries with a constant current at initial stage. At the same time, the battery voltage keeps increasing until reaching the constant charge voltage point. Then, the charge current will decrease accordingly, now it’s in second stage.
  • Page 10 5. Picture of the UPS 30k picture single input dual input...
  • Page 11 30k UPS inner picture 60K picture...
  • Page 12 60K picture 60K unit inner picture...
  • Page 13 Front panel Rear panel Left panel 100K~200K picture...
  • Page 14 Right side panel Top side panel 100K~200K picture...
  • Page 15: Function Explanations For Each Pcb

    6. Function explanations for each PCB Table 5.1 PCBA information of Smartbitt 3-3 10~80k Mode Part number Function Picture 31-531408- INV board 31-531407- PFC board 72-300745- Control board 200K 72-300744- Control board 200K...
  • Page 16 71-304525- Input fuse EMI board 72-300820- Communicatio Rack XXG(LCD) board 72-300746- XXG(LCD) Towe 72-300773- XXG(Touch 200K panel) tower 31-531225- Parallel board 200K 31-531366- SPS board 31-531025- R PFC board...
  • Page 17 200K 31-531252- ST PFC board 31-531026- INV Board 200K 31-531253- AC IN Board 200K 31-531254- Bypass board 200K...
  • Page 18 31-531255- Charger board 200K 71-600400- Charger fuse board 200K 71-304252- SNMP card power supply 200K board 71-300194- EMBS board 200K...
  • Page 19 71-303357- Touch panel power board 200K (71-304615- advance communicatio n board) Note: “XX” in the serial number is the version of the PCB. It may be modified according to releasing version in the future.
  • Page 20 7. Interface 7.1 LED Display Table 6.1 LED Display MODE Bypass Line Battery Fault UPS Startup ● ● ● ● No output ○ ○ ○ ○ Bypass mode ● ○ ○ ○ Line mode ○ ● ○ ○ Battery mode ○...
  • Page 21 7.3 LCD Display Icon Display Function Backup time information Indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, M: minutes, S: seconds Fault information Indicates that the warning and fault occurs. Indicates the fault codes, and the codes are listed in details in section 3-9.
  • Page 22 7.4 4.3 Inch and 5 inch and 7 inch touch panel display 7.5 4.3 Inch and 5 inch and 7 inch touch panel password The Primary password is “0000”, this password can set UPS function. The Factory password is “XXXX”, this password can calibrate the parameter and change all parameter. Only factory and after-sales Service person have this password.
  • Page 23: Troubleshooting

    8. Trouble Shooting This section describes how to find the troubles when UPS is abnormal. We suggest you to follow the service procedure below: 1. Check the UPS status via LED and LCD display, the sound of the buzzer and get the warning or fault code via the RS232 if possible, otherwise listen to the description of end users.
  • Page 24 1 Beeping / second Line connect different Check the R/S/T input 1 Beeping / second Bypass connect different Check R phase input 1 Beeping / second Parallel load different Check the output cable Locked bypass after 1 Beeping / second Check the loads overload 3 times in 30min 1 Beeping / second...
  • Page 25 8.1.2 Trouble shooting for fault codes in LCD display When the UPS is fault, it will transfer to Fault mode. 7.1.2.1 Fault code for 10k~80k Code Fault Event Description Action icon When the bus voltage can’t Check if power components such as IGBT and reach the setting value in SCR for the PFC and the utility power SCR are None...
  • Page 26 displayed. When INV phase L3 output voltage keeps lower and Inverter L3 output current keeps output short higher than normal, the fault signal will be displayed. Inverter L1L2 When INV phase L1- output short phase L2(Line to line) voltage keeps lower and output current keeps higher than normal, the fault signal will be displayed...
  • Page 27 form the inverter voltage INV relay and bypass SCR None wiring fault open, but output voltage is Check the input and output wires higher than normal. When parallel communication between Check the parallel cables between the UPSs None communication the UPSs is interrupted, the are normal, and the cable between the parallel fault signal...
  • Page 28 voltage difference Inverter between inverter None waveform reference inverter abnormal sample is greater than normal voltage difference Check the load is not overload and no surge Inverter between inverter load ,Check the Inverter circuited None waveform reference inverter sample is greater than abnormal normal voltage...
  • Page 29 The unit have detected L1 INV IGBT over None IGBT fault signal from the current fault drive board The unit have detected L2 INV IGBT over Check the IGBT drive signal and INV IGBT None IGBT fault signal from the circuited current fault drive board...
  • Page 30 Model Type Pin1&pin2 Pin3&pin4 Pin5&pin6 Pin7&pin8 30KL 60KL 100KL 120KL 180KL 200KL Note : “1” indicates that the jumper is connected; “0”indicates that nothing is connected, For long run model, The 30KL’s charge board on the INV board (71-304125-XXG)。The 30KL’s default charging current is 4A for battery configuration.
  • Page 31 2. After completing the setting, you can type the command in the command area. 3. +BUS voltage regulation: Type “BUSP+/- XX” command (XX is two digits from 00 to 99). Then press the “ENTER” key, and +BUS voltage will rise (drop) about 0.1V. 4.
  • Page 32 UC9, UC10, UC11 UC12 D9,D10,D19,D20,D29,D30 Diode Short or open Q1,Q2, Q5,Q6, Q9,Q10 IGBT C-E short or open 30K INV Section Circuit Block Checked components Component Type Failure condition A-K Short or open Q40,Q17,Q43,Q21,Q23,Q45, Q30,Q32,Q33,Q41,Q44,Q46 D38,D41,D40,D47,D58,D57 Diode Short or open Q13,Q14,Q15,Q16,Q22,Q18,Q20,Q19,Q25,Q26,Q27,Q28 IGBT C-E short or open DC FUSE...
  • Page 33 8.2.4.2 30K Major parameters of Bypass and INV and 12A Charger section。 Reference Failed Checked components Instrument function Value condition »44MΩ (A, K) Resistance Short or open Q40,Q17,Q43,Q21,Q23,Q45, »17Ω (G, K) Resistance Short or open Q30,Q32,Q33,Q41,Q44,Q46 R29,R201,R211,R39,R233,R40,R451,R453,R32 »33Ω Resistance Short or open 1,R66,R454,R457 »0.38V (E, C)
  • Page 34 Line I/P FUSE F1,F2,F3,F4,F5,F6, Fuse Open 60-200K BAT FUSE Section Circuit Block Checked components Component Type Failure condition BAT I/P Fuse F1,F2,F3,F4 Fuse Open 18A Charger Section Circuit Block Checked components Component Type Failure condition DC FUSE F1,F2, F3, F4 Fuse Open MOSFET...
  • Page 35 R5,R6,R7,R8,R9,R10,R24,R25,R61,R62,R76,R »33Ω 77,R111,R112, Resistance Value change R126,R127 »0.38V (E, C) Diode Voltage Droop Short or open »1.0V Q1,Q2, Q5,Q6, Q9,Q10 (E, G) Diode Voltage Droop Short or open »50KΩ (G, E) Resistance Short or open »10Ω R26,R27,R78,R79, R128,R129 Resistance Short or open »0.372V D9,D10,D19,D20,D29,D30 Diode Voltage Droop...
  • Page 36 »17Ω (G, K) Resistance Short or open »33Ω R29,R201,R211,R39,R233,R40 Resistance Short or open (E, C) Diode Voltage Droop »0.38V Q13,Q14,Q15,Q16,Q2 »1.0V 2,Q18,Q20,Q19,Q25, (E, G) Diode Voltage Droop Q26,Q27,Q28 »50KΩ (G, E) Resistance »10Ω R155,R158,R188,R328,R195,R198 Resistance Short or open »33Ω R196,R197,R328,R178,R156,R157 Resistance Short or open »22Ω...
  • Page 37 8.2.4.6 30-200K Major parameters of SPS section。 30-200K SPS Section Reference Failed Checked components Instrument function Value Condition F1,F2,F3,F4, F5, F6, F9, F10, F11, F12 Resistance < 0.5 Ω Open D6,D13,D14,D7,D8,D10,D11,D12,D16,D17,D18,D19,D20, »0.59V Diode Voltage Droop Short or open D21,D22,D23,D24,D27 »0.425V D32,D35,D25,D26 Diode Voltage Droop Short or open...
  • Page 38 HV30KL/LV15KL Single Input Mode...
  • Page 39 HV30KL/LV15KL Dual Input Mode Input Neutral on the SPS board Below is the step transfer to Maintain bypass mode: 1, if the UPS work in online mode, please turn off the UPS to bypass mode. 2, Removing the cover of the Maintain bypass, then the UPS will force transfer to bypass mode and the warning 3A will alarm.
  • Page 40 HV60KL/LV30KL Dual Input Mode Below is the step transfer to Maintain bypass mode: 1, if the UPS work in online mode, please turn off the UPS to bypass mode. 2, Removing the cover of the Maintain bypass, then the UPS will force transfer to bypass mode and the warning 3A will alarm.
  • Page 41 9.3 HV120KL~200KLmode transfer to Maintain Bypass mode Below is the step transfer to Maintain bypass mode: 1, if the UPS work in online mode, please turn off the UPS to bypass mode. 2, Removing the cover of the Maintain bypass, then the UPS will force transfer to bypass mode and the warning 3A will alarm.
  • Page 42 How to set the parameter 10.1 How to set the charger current 10.1.1 PF0.9 unit with standard LCD set charger current Power on the unit with battery, but don’t start up the unit. Then send the command. Noted1: Enter the “^S009CHMC04.0” command and click “Send”. UPS will return “^D006ACK”...
  • Page 43 command is ^S009CHMC01.0 to ^S009CHMC4.0) 10.1.2 PF1.0 unit with standard LCD set charger current Power on the unit with battery, but don’t start up the unit. Then send the command. Noted1: Enter the “^S009CHMC04.0” command and click “Send”. UPS will return “^D006ACK”...
  • Page 44 10.1.3 PF1.0 unit with touch panel set charger current Power on the unit with battery, but don’t start up the unit. Then send the command.
  • Page 45 This parameter setting is will be saved only when UPS shuts down normally with battery connection.
  • Page 46 10.2 Dynamic Password Description...
  • Page 47 11.1 What is the DC Source? The Smartbitt SBOL series Unit DC Source is made up by two chargers, you can use it as Smartbitt 33 Battery external charger, and it also can use as DC Source to self-test the Smartbitt 33 Unit.
  • Page 48 Picture3: the charger output voltage adjustment picture 11.2 How to set the UPS’s parameter before self-test the Smartbitt SBOL Unit? a, if your unit’s battery number is ±16pcs(16+16 for HV unit), you also need to set the DC Source battery number to ±16pcs(16+16). If your battery number is ±20pcs, you also need to set the DC Source battery number to ±20pcs.
  • Page 49 ^S007SETBAT ^S010SBATPCS16 for “+96V / -96V” battery pack ^S007SETBAT ^S010SBATPCS18 for “+108V / -108V” battery pack ^S007SETBAT ^S010SBATPCS20 for “+120V / -120V” battery pack This command will be effective and you should turn off UPS with battery connected to save the change.
  • Page 50 Noted1: if the UPS return “D006NAK…”, it is means your setting is not successful. Noted2: if you have set the parameter successful, you also need to turn off the input mains and let UPS into standby mode with battery until UPS Shutdown automatic, don’t turn off the battery before the UPS Shutdown, because the UPS is saving your new parameter to the system.
  • Page 51 Figure 8.3.3 Figure 8.3.4 Step3: Press the “UP” Button and the “DOWN” Button at the same time, and you will enter into a set interface. Press the “UP” Button or “DOWN” Button until you can see the interface likes figure8.3.5. Press the “ON” button and set the self-checking program form disable status to enable status likes figure8.3.6.
  • Page 52 Figure 8.3.7 Figure 8.3.8 Refer above the standard LCD self-test step, for touch panel UPS self-test, it is need to press the “POWER ON” button to start up the SPS, then you can refer below picture to do the self-test step. Settingàadvanceàpassword “0729”àUPS self-testàStart...
  • Page 53 11.5 Process of self-checking program PFC 1 Check the Battery voltage detect circuit PFC 2 Check the BUS voltage detect circuit PFC 3 Check the PFC IGBT Drive circuit PFC 4 Check the Battery SCR circuit PFC 5 Check the Line SCR circuit PFC 6 Check the BUS voltage detect circuit again PFC 7...
  • Page 54 12. Appendix 12.1 Basic communication command In this section, we will show you some basic communication commands that will help you debug or regulate the UPS system. 12.1.1 ^P005Q3GS<0x0d> ^P005Q3GS<0x0d> means to request general status parameters of the system. The command format is: Computer: ^P005Q3GS<0x0d>...
  • Page 55 Bypass mode UPS Failed EPO active Test in Progress Shutdown Active mute status (bat silence) battery test ok 12.1.2 ^C010BUSPV+NNN<0x0d> This command is to adjust the positive BUS voltage, the format is: Computer: ^C010BUSPV+NNN<0x0d> UPS: (ACK or (NAK* *: If UPS accepts this command, responds ACK. Otherwise, responds NAK Voltage adjustment step: <nnn>.
  • Page 56 12. 1.5 ^C010BATNV+NNN<0x0d> This command is to adjust the negative battery voltage sampling value. You can adjust the parameter to the sampling voltage displayed on LCD and the real battery voltage. The format is: Computer: ^C010BATNV+NNN<0x0d> UPS: (ACK or (NAK* *: If UPS accepts this command, responds ACK.
  • Page 57 UPS: (1000000000000000000000000000000000000000000000000000000000000000 Meanings: The battery of UPS disconnected.