FIRE SUPPRESSION SYSTEM FOR
PROFESSIONAL KITCHENS
DIAS
INSTRUCTIONS MANUAL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DIAS and is the answer not in the manual?

Questions and answers

Summary of Contents for Mobiak DIAS

  • Page 1 FIRE SUPPRESSION SYSTEM FOR PROFESSIONAL KITCHENS DIAS INSTRUCTIONS MANUAL...
  • Page 2 MVK-MAN-DIAS-REV.4, 17/09/2018...
  • Page 3: System Operation

    20°C) prevents any damage to surfaces made of stainless steel found in Professional Kitchens. Dias Fire Detection-Suppression System is designed by MOBIAK for protecting Kitchen Devices under Kitchen Hood, the Kitchen Hood itself and the Hood Air Ducts. The system consists of a Wet Chemical Local Application Fire Extinguisher of both Automatic and Manual operation, Control Panel, Fire Detection Unit and Discharge Nozzles designed for protecting different Kitchen Devices.
  • Page 4 Note: the Control Panel used on Dias System offers the user Fuse Activation Time Delay from 0-80 seconds. This means that if the Time Delay is been configured to 40secs, Extinguisher’s Valve Fuse Activation will take place after 40secs. Practically, this delay offers the user the i.e.
  • Page 5 Fire Detection-Suppression Panel with Battery including Extinguish Button, Siren with MBK12-ZEUS-PANEL Beacon, Relay for Electrical Power Shut down & Extinguish Cancel Switch BS-534 System Activation Call Point (electrical) MBK13-ACTIV-WIRE System Activation Metal Wire Mechanism (mechanical) MBK13-DIAS-INS Usage Instructions Sign – For installation in Kitchen MVK-MAN-DIAS-REV.4, 17/09/2018...
  • Page 6 Important: The System consists of specific Components approved by MOBIAK. Any change on the components given on this Manual is forbidden by the manufacturer as it will affect system’s operation. The Discharge Nozzles (½” Male Thread) are made of Stainless Steel and come with white colour incombustible Silicon Protection Cap.
  • Page 7: Flow Units

    Stainless Steel Flexible Hose, Stainless Steel tubes (φ18) and Stainless Steel Components as nipples, 90° corners and tee pieces consists the Hydraulic Pipe Network of ZEUS System that leads the extinguishing agent from the fire extinguisher to the nozzles from where it is discharged. MVK-MAN-DIAS-REV.4, 17/09/2018...
  • Page 8: Important Installation Instructions

    Note 3: Stainless Steel Tubes and Components required for the construction of the System’s Pipe Network are not traded by MOBIAK and must be supplied from local market. LINEAR HEAT DETECTION CABLE Linear Heat Detection Cable is a fixed temperature sensor of activation temperatures 138°C, 180°C or 250°C.
  • Page 9 6.4 cm radius. Do not use wire nuts or other similar devices. All connections must be made via  MOBIAK’s porcelain splicing connectors. Do not paint this detector, per UL and FM requirements. ...
  • Page 10 Cable of the Fire Detection Panel ( MOB-2001 is been factory connected to Suko Plug so that to be directly connected to a usual as shown in following pictogram plug of the kitchen ( MVK-MAN-DIAS-REV.4, 17/09/2018...
  • Page 11: System Inspection

    Visual Inspection of the System is recommended once per month by Kitchen Owner or Personnel. Note: Inspection is possible to be performed from the Kitchen Owner or Personnel only in case the training has successfully been completed by MOBIAK or any of its Authorized System Integrators. The procedures are the following: Fire Extinguisher Valve Rod, Visual check of the System’s Manual Triggering Mechanisms (...
  • Page 12 SYSTEM SERVICE/MAINTENANCE System’s maintenance must be always performed only by Authorized Maintenance Technicians properly qualified and trained by MOBIAK or by any of MOBIAK’s Authorized System Integrators. Note: Maintenance Technicians can be trained by owners of Fire Fighting Equipment Stores only in case that the owner holds a Training Certificate on the Fire Suppression System issued only by MOBIAK.
  • Page 13 SYSTEM REFILLING The local application Fire Extinguisher of the Fire Suppression System should always be refilled exclusively with Wet Chemical Agent approved by MOBIAK, in any of the following cases: Immediately after five (5) years from the production date of the Fire Extinguisher, ...
  • Page 14: Inspection Form

    INSPECTION FORM Α/Α DATE TECHNICIAN FULL NAME DESCRIPTION OF SERVICES SIGNATURE -13- MVK-MAN-DIAS-REV.4, 17/09/2018...
  • Page 15: Maintenance Form

    MAINTENANCE FORM Α/Α DATE TECHNICIAN FULL NAME DESCRIPTION OF SERVICES SIGNATURE -14- MVK-MAN-DIAS-REV.4, 17/09/2018...