C7012A,C,E,F,G SOLID STATE PURPLE PEEPER® ULTRAVIOLET FLAME DETECTORS
TERMINAL STRIP
FOR R4075E
ON SUBBASE
1
G
F
13
12
3
L2
AN R7247C DYNAMIC SELF-CHECK AMPLIFIER MUST BE USED WITH
1
AN R4075E.
TWO C7012E OR F DETECTORS CAN BE CONNECTED IN PARALLEL
2
TO THE SAME TERMINALS ONLY ON 120 VOLT CONTROLS.
3
WIRING IS SHOWN FOR SECTION B. CONNECT ANOTHER DETECTOR
TO THE IDENTICAL TERMINALS IN SECTION A. TERMINAL L2 IS
USED FOR BOTH SECTIONS.
4
VOLTAGE AND FREQUENCY RATING OF THE C7012E OR F MUST
MATCH THE POWER SUPPLY OF THE FLAME SAFEGUARD CONTROL.
5
( ) IDENTIFICATION LABEL ON LEADWIRES.
Fig. 12. Wiring diagram for C7012E or F Detectors with
R4075E (currently obsolete) Flame Safeguard Control.
TERMINAL STRIP
FOR R4138C OR D
1
IN CABINET
OR ON SUBBASE
14
13
12
F
G
9
3
8
7
3
JUMPER
L1
4
L2
1
AN R7247C DYNAMIC SELF-CHECK AMPLIFIER MUST BE USED WITH
AN R4138C OR D.
2
TWO C7012E OR F DETECTORS CAN BE CONNECTED IN PARALLEL
WITH THE SAME TERMINALS ONLY ON 120 VOLT CONTROLS.
3
REMOVE THE JUMPERS BETWEEN TERMINALS 14 AND 13 AND
BETWEEN TERMINALS 12 AND F (IF THERE ARE JUMPERS),
AND INSTALL A JUMPER BETWEEN TERMINALS 13 AND 7.
4
VOLTAGE AND FREQUENCY RATING OF THE C7012E OR F MUST
MATCH THE POWER SUPPLY OF THE FLAME SAFEGUARD CONTROL.
( ) IDENTIFICATION LABEL ON LEADWIRES.
5
Fig. 13. Wiring diagram for C7012E or F Detectors with
R4138C,D (currently obsolete) Flame Safeguard controls.
60-2398-17
C7012E,F
2
YELLOW
BLUE
(L2)
WHITE
(S)
WHITE
5
(L2)
BLACK
(L1)
BLACK
4
L1
(POWER SUPPLY)
M9373
2
C7012E,F
(S)
WHITE
BLUE
YELLOW
(L2)
WHITE
5
(L1)
BLACK
(L2)
BLACK
M9374
TERMINAL STRIPS FOR R4140 OR
BC7000 ON Q520A WIRING SUBBASE
L1
2
L2
F
1
AN R7247C DYNAMIC SELF-CHECK AMPLIFIER MUST BE USED WITH
AN R4140, BC7000.
2
VOLTAGE AND FREQUENCY RATING OF THE C7012E OR F MUST
MATCH THE POWER SUPPLY OF THE FLAME SAFEGUARD CONTROL.
3
TWO C7012E OR F DETECTORS CAN BE CONNECTED IN PARALLEL
WITH THE SAME TERMINALS ONLY ON 120 VOLT CONTROLS.
4
THE ADDITIONAL YELLOW/GREEN LEADWIRE IS ONLY ON C7012E
MODELS DESIGNED TO MEET DIN OR BGC REQUIREMENTS;
CONNECT THIS WIRE TO A SEPARATE GROUND TERMINAL ON THE
WIRING SUBBASE.
5
( ) IDENTIFICATION LABEL ON LEADWIRES.
Fig. 14. Wiring diagram for C7012E or F Detectors with
R4140, and BC7000 (currently obsolete), and R7140 Flame
Safeguard controls.
BCS 7700
1
TERMINAL STRIP
31
29
27
L2
L1
L2
1
A R7747C DYNAMIC SELF-CHECK AMPLIFIER MUST BE USED
WITH THE C7012E,F/BCS 7700 COMBINATION. SHUTTER
CYCLE RATE IS 12 TIMES PER MINUTE. USE SERIES 7 OR
GREATER FOR THESE APPLICATIONS.
2
VOLTAGE AND FREQUENCY RATING OF THE C7012E,F MUST
MATCH THE POWER SUPPLY OF THE FLAME SAFEGUARD
CONTROL.
3
TWO C7012E,F DETECTORS CAN BE CONNECTED IN PARALLEL
TO THE SAME TERMINALS ONLY ON 120 VOLT CONTROLS.
THE ADDITIONAL YELLOW/GREEN LEADWIRE IS ONLY ON
4
C7012E MODELS THAT MEET BGC OR DIN REQUIREMENTS;
CONNECT YELLOW/GREEN WIRE TO A SEPARATE GROUND
TERMINAL ON THE WIRING SUBBASE.
( ) IDENTIFICATION LABEL ON LEADWIRES.
5
Fig. 15. Wiring diagram for C7012E,F Detectors
with BCS 7700 (currently obsolete) Flame Safeguard
10
1
17
G
C7012E OR F
3
4
YELLOW
YELLOW/GREEN
5
(S)
WHITE
(L2)
WHITE
(L1)
BLACK
(L2)
BLACK
BLUE
M9375A
2
3
C7012E,F
BLUE
YELLOW
(S)
WHITE
5
(L2)
WHITE
(L1)
BLACK
(L2)
BLACK
YELLOW/GREEN
4
M9376
controls.