Pre-Installation Checklist - Joslyn TransEnd 50 Installation, Operation And Maintenance Manual

Surge suppression filter systems
Table of Contents

Advertisement

Purpose and Applications
of TransEnd Products
The Importance of Correct
Installation
W A R N I N G !

Pre-Installation Checklist

JOSLYN
TRANSEND
INSTALLATION, OPERATION AND MAINTENANCE MANUAL ISSUED 6.01
®
The versatile TransEnd product family is designed for facility-
wide installation. TransEnd uses proven Metal Oxide Varistors
(MOVs) and an efficient capacitive filter system to reduce or
eliminate transients, impulses and high-frequency noise within a
building's electrical system.
This manual provides guidelines for the proper installation of
TransEnd devices. Proper product selection and compliance with
these guidelines will help your new suppression system provide
years of reliable service. If installers are unsure about the facility's
electrical configuration or have other installation-related ques-
tions, we recommend they consult with a master electrician or
other qualified electrical professional.
When shortcuts are taken or installation procedures are not
followed, the TransEnd system may be damaged or may not pro-
vide adequate protection. Improper installation may also void the
warranty. It is extremely important to follow these installation
procedures carefully.
This manual is designed to step you through the easy installa-
tion procedures. However, should you have questions about
installing TransEnd, please call Joslyn Technical Support at
800.238.5000.
WARNING! The TransEnd's Warranty is voided if the unit is dam-
aged as a result of improper installation or the installer's failure
to verify the following conditions prior to installation.
➤ Confirm that the voltage(s) and power configuration shown
on the TransEnd product label are consistent with the voltage and
service configuration at the TransEnd installation site. One of the
following voltage and service configurations is printed on the
label affixed to the TransEnd:
Product Label Designation
System Voltage, Service Configuration
XNxxx-120/240-2G
120/240VAC, 1ø 3-wire SPLIT-PHASE, w/ground
XNxxx-120/208-3GY
120/208VAC, 3ø 4-wire WYE, w/ground
XNxxx-220/380-3GY
220/380VAC, 3ø 4-wire WYE, w/ground
XNxxx-277/480-3GY
277/480VAC, 3ø 4-wire WYE, w/ground
XNxxx-120/240-3GHD
120/240VAC, 3ø , high-leg DELTA, w/ground
(B phase must be 208V)
XNxxx-240-3DG
240VAC, 3ø , 3-wire DELTA, w/ground
XNxxx-380-3DG
380VAC, 3ø , 3-wire DELTA, w/ground
XNxxx-480-3DG
480VAC, 3ø , 3-wire DELTA, w/ground
xxx Denotes product's surge current rating.