Volt:prot; Command Summary - Agilent Technologies 664xA Programming Manual

Gpib dc power supplies
Hide thumbs Also See for 664xA:
Table of Contents

Advertisement

VOLT:PROT

This command sets the overvoltage protection (OVP) level of the power supply. If the output voltage exceeds the OVP
level, then the power supply output is disabled and the Questionable Condition status register OV bit is set (see "Chapter 4 -
Status Reporting"). An overvoltage condition can be cleared with the OUTP:PROT:CLE command after the condition
that caused the OVP trip is removed. The OVP always trips with zero delay and is unaffected by the OUTP:PROT:DEL
command.
Returned Parameters

Command Summary

This summary lists all power supply subsystem commands in alphabetical order, followed by all common commands in
alphabetical order. See Table 3-1 for the command parameters accepted by each power supply model.
Command
ABOR
CAL
[SOUR]:CURR[:LEV][:IMM][:AMPL]
[SOUR]:CURR[:LEV][:IMM][:AMPL]?
[SOUR]:CURR[:LEV]:TRIG[:AMPL]
[SOUR]:CURR[:LEV]:TRIG[:AMPL]?
[SOUR]:CURR:PROT:STAT
(SOUR]:CURR:PROT:STAT?
[SOUR]:DIG:DATA[:VAL]
[SOUR]:DIG:DATA[:VAL]?
DISP[WIND]:MODE
DISP(WIND]:MODE?
DISP[:WIND][:STAT]
DISP[:WIND][:STAT]?
DISP[:WIND]:TEXT[:DATA]
DISP[:WIND]:TEXT[:DATA]?
INIT[:IMM)
INIT:CONT
INIT:CONT?
Command Syntax
*Alternate Syntax
Parameters
Default Suffix
*RST Value
Examples
Query Syntax
Related Commands
* Available to accommodate earlier power supply programs.
Command Summary
Subsystem Commands
[SOURce]:VOLTage:PROTection[:LEVel] <NRf+>
[SOURce]:VOLTage:PROTection:AMPLitude <NRf+>
Table 3-1
V
MAX
VOLT:PROT 21.5
VOLT:PROT:LEV MAX
VOLTAGE:PROTECTION:LEVEL 145E-1
[SOURce]:VOLTage:PROTection[:LEVel]?
[SOURce]:VOLTage:PROTection [:LEVel]? MIN
[SOURce]:VOLTage:PROTection [:LEVel]? MAX
<NR3> VOLT:PROT? returns presently programmed OVP level.
VOLT:PROT? MAX and VOLT:PROT? MIN return the
maximum and minimum programmable OVP levels.
OUTP:PROT:CLE
*RST
(none)
(See Appendix A in the Operating Manual)
<NRf+>[suffix]
(none) |MIN|MAX
<NRf+>[suffix]
(none) |MIN|MAX
0 |l | ON|OFF
(none)
<NRf>
(none)
NORM|TEXT
(none)
0 |l | OFF|ON
(none)
<STR>
(none)
(none)
0 | l | OFF|ON
(none)
*SAV
*RCL
Parameters
Language Dictionary
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

665xa667xa668xa669xa

Table of Contents