CX-92S TDS Series Magnetic Locks
INSTA L L AT I O N I NST RU CTI ONS
3. INSTALLATION
1. Drill the armature plate holes in the door using the sticker
template provided.
2. Attach the armature plate to the door with the hardware
provided as per Figure 2.3.
3. With the door closed, mark the door frame at the edge of
the armature in order to properly align the electromagnet
to the armature.
4. Attach the mounting plate to the door frame using the self-
tapping screws provided.
Align the mounting plate with the mark from Step 3.
5. Insert the wires through the hole in the mounting plate and
into the electromagnet unit. Attach the electromagnet unit
to the mounting plate with the Allen head fixing screw.
6. Screw in the anti-tamper nuts to prevent unauthorized
access and make sure to fully tighten the fixing screw with
proper tool. A "T" Handle Allen Key.
7. The electromagnetic lock must be installed in accordance
with the following :
Life Safety Code ANSI / NFPA 101.
Local Authority having Jurisdiction.
Manufacturer's installation instructions provided with
each unit.
The power supply units must be mounted inside the
secured or protected area.
8. Connect the magnetic contact wire to the door monitoring
system; according to the system guides.
9. Typical wiring method shall be in accordance with CSA
C22.1, Canadian Electrical Code, Part I, Safety Standard for
Electrical Installations, Section 32.
Note:
Install in indoor dry location.
Use caution when changing factory default setting.
It is recommended to apply a light coat of silicon lubricant to
the mating surface on a monthly basis to prevent rust.
NOTICE:
All models are recognized to:
UL 294 and ULC S533-15 : Standard for Access & Egress.
Models CX-91S-06 & CX-91S-12 are listed to:
UL 1034, Standard for Burglary-Resistant Electric
Locking Mechanism.
UL 294, Access Control System Units
** Value not verified by UL.
Remark:
All drawings shown are for illustration purpose only.
Actual product may vary due to product enhancement.
Opening New Doors to
Innovation, Quality and Support!
Page 2 of 2
4. TROUBLE SHOOTING
1. Sensor not functioning:
- Improper attachment of electromagnet and armature plate.
- Modification of the PCB
2. Door not locked:
- Incorrect wiring or no power from power supply
3. Reduced holding force:
- Poor contact of electromagnet and armature
- Be sure armature is loose enough that it can fully contact
electromagnet along the entire length
- Mating surface is dusty or damaged
- Improper input voltage or wire size.
Door Contact Sensor;
Max. Contact Rate: 40VDC,0.25A
LED Status:
> Red = Locked
> Green = Released
> Off = No Input
(Only for LED-TB Models)
12 VDC
Setting
Call: 1.877.226.3369 / 905.366.3377
Visit: www.camdencontrols.com
White Wire (Mag. Ctc.)
White Wire (Mag. Ctc.)
PUSH SWITCH
POWER
SUPPLY
DRY CONTACT
12V/24V
+
-
PS C NO NC
24 VDC
Setting
IMPORTANT!
Set the jumper position according to the power
input correctly before switch ON the power.
File: EISB-EMS-IG (Page 1-2) Ver. A/ 11.03.2020
Camden Part No.:
Timer
5 sec
1
2
0-0
10 sec
1
2
0-1
15 sec
1
2
1-0
25 sec
1
2
1-1
40-82B220