READ INSTRUCTIONS BEFORE INSTALLING

Essential safety Informations

· This product is for indoor use only IP20, do not use in damp or wet locations.
· Mains voltage must be switched off before mounting, maintenance.
· This track must be installed and maintained by a suitably qualified person in compli-
ance with latest installation and safety regulations.
· Installation and operating of this Track is subject to national safety regulations.
. The manufacturer is not liable for damage caused by improper use or installation.
· Only ceiling mounted.
· Material used for ceiling fixation should be conform to the relevant building regulation.
· It is the responsibility of the installer to ensure the electrical, mechanical and thermal
compatibility of the track-system and the fittings.
· Save these instructions.
Wire selection & power
1. Wire section
distance power supply to track
5m
10m
30W
1.5
1.5
60W
1.5
1.5
90W
1.5
1.5
120W
1.5
1.5
150W
1.5
1.5
180W
1.5
1.5
210W
1.5
1.5
240W
1.5
1.5
270W
1.5
1.5
300W
1.5
1.5
Always choose for a power supply with at least 10% overcapacity compared to the sum of the total
power installed in the track.
steel
aluminum
15m
20m
25m
30m
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2
1.5
1.5
2
2.5
1.5
1.5
2
2.5
1.5
2
2.5
3
1.5
2
2.5
3
2.5
2.5
3
4
choose the right tool
to cut the track
MAX POWER
Bloc 300
40m
Bloc 600
1.5
1.5
1.5
2
2.5
3
3
Example
4
- a track of 6m with 10 x bloc 300 (10x14.4W=144W)
4
- distance between power supply and track is 40m
5
 in this particular case you need a 2.5mm² wire section
°bloc - installation manual - 1/5
14.4W
28.8W

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Bloc 300 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eden Bloc 300

  • Page 1 150W 180W 210W Example 240W - a track of 6m with 10 x bloc 300 (10x14.4W=144W) 270W - distance between power supply and track is 40m 300W  in this particular case you need a 2.5mm² wire section Always choose for a power supply with at least 10% overcapacity compared to the sum of the total power installed in the track.
  • Page 2 ungdes Kopfstücks Kabel4x1,5 mm verwenden. DieAbdeckungdes Kopfstücksabnehmen, indem die 3SchraubenA1-A2-A3 (Abb.10) abgeschraubtwerden, um an die IT -Tutti gli adattator °bloc - installation manual - 2/5 ezugelangen.DieabnehmbareWand1oder2durchstoßenunddurchdasentstandeneLochdaselektrischeKabelhindurchführen.AnschließendjenachverwendetemLoch sono previsti in due t en des Kabels durch die Verschlusskappe oder die Schiene ebenfalls ein Loch bohren (Abb. 11). Die äußere Hülle von den Kabeln abziehen und diese ablängen (Abb. 12), e 9529…-K...
  • Page 3 24Vdc °bloc - installation manual - 3/5 Bus dati Step 2: CONNECTING END FEEDER to 48Vdc and data 1. Open preferred cap for cable access 2. Remove the cover by loosing 3 screws 65-70 20-25 3. Connect cables (see indications inside) 65-70 20-25 48 Vdc...
  • Page 4 °bloc - installation manual - 4/5 Option 2 - Integrated powersupply 110/240 Vac to 48 Vdc power supply 48Vdc 110/240V Track Feeder dali/1-10V* Electrical circuit must be switched off when installing feeders input 240 Vdc Powersupply PS.48.60.VLM PS.48.100.VLM (output 48Vdc) 65-70 20-25...
  • Page 5 °bloc - installation manual - 5/5 Step 3: INSTALL BLOC’s ON THE TRACK . Start installing the first fixture at the beginning of the track . Install one by one in the correct order . All fixtures are attached with springs Not straight Straight positioned positioned...

This manual is also suitable for:

Bloc 600

Table of Contents