Download Print this page

Lexicomm Solo LX228 Quick Start Manual

Evcs master station

Advertisement

Quick Links

Lexicomm Solo EVCS
Master Station Quick Start Guide
The LX228 Solo master station is a ready out of the box EVC system suitable for standalone
applications up to 8 lines. It is very simple to install, requiring no set up or software, and is
compatible with Vox Ignis range of Type A, Type B, Type C outstations and the Assist Call
range of emergency assistance alarms.
This guide summarises applicable information from the full
manual, which is available by scanning this QR code.
Figure 1
1.
Mounting Information
Master stations should be mounted in fire control rooms or next to the fire alarm panel at a
mounting height of between 1.4 and 1.5m above finished floor level to the centre of the
controls. Type A outstations (fire telephone) are generally fitted in fire-fighting lobbies and
fire and rescues access points at 1.3 to 1.4m above (FFL). Type B outstations are used in
disabled refuges at a mounting height of 0.9m to 1.2m (FFL). For Emergency assistance
alarms see ViLX-ACA datasheet.
2.
Cable Information
Fire telephone systems utilise Type A outstations and must use enhanced grade fire resistant
cabling throughout for all wiring, including the mains supply to the master station. Max
distance using 1mm or 1.5mm cable is 500m from outstation to master station.
Disabled Refuge systems utilise Type B outstations, they are wired in standard or enhanced
grade fire resistant cabling Refer to BS 5839-9:2021 for full details.
Max distance using 1mm or 1.5mm cable is 500m from outstation to master station.
Emergency assistance alarms (Assist Call) for dedicated circuits use 1mm 2 core flex for
lengths of 500m from the master or security cable for shorter lengths from up to 50m for 2
cores up to 200m if 4 cores are twisted together. If sharing with a Type B use the same
grade of fire resistant cable.

Advertisement

loading
Need help?

Need help?

Do you have a question about the Solo LX228 and is the answer not in the manual?

Questions and answers

Summary of Contents for Lexicomm Solo LX228

  • Page 1 Lexicomm Solo EVCS Master Station Quick Start Guide The LX228 Solo master station is a ready out of the box EVC system suitable for standalone applications up to 8 lines. It is very simple to install, requiring no set up or software, and is compatible with Vox Ignis range of Type A, Type B, Type C outstations and the Assist Call range of emergency assistance alarms.
  • Page 2 Important Safety Information This Equipment must only be installed and maintained by a suitably skilled and competent person. This Equipment is defined as Class 1 in EN IEC62368-1:2020+A11:2020 (Low Voltage Directive) and must be EARTHED. Caution Indoor Use Only Shock Hazard- Warning Isolate Before Opening TO REDUCE THE RISK OF FIRE OR...
  • Page 3 Installation Use the 2.5mm AF Hex Key supplied to open the right-hand front cover. Mains Connections Supply Relay Contacts Figure 3 Figure 4 Unused knockouts must be left unopened to comply with the Low Voltage Directive. Accidentally knocked out holes should be blanked off. The ViLX-228S Master Station weighs 6kg with batteries, so care should be taken to securely mount the Station on stud walling.
  • Page 4 To accept the fault, enter either the access level 2 (code: 1664) or access level 3 (code: 1812) menu, then press zone button 1. The Lexicomm ViLX-228 EVCS is designed and manufactured in the UK by: Vox Ignis Limited, Unit 27, NEBIC, Enterprise Park East, Sunderland, SR5 2TA.