CHAPTER 3: PRODUCT USE
3.6 CALIBRATING THE ISOLATED DIGITAL VOLTMETER
The calibration of the EME1D1-005-R2 sensor can only be performed in a Gateway GUI. Normally the senor will not
need calibration. It is good practice, however, to calibrate it at least once a year depending on the level of usage.
To calibrate the sensor:
1.
Disconnect the CATx extension cable and connect the calibration cable following the labels indicating which end
is connected to either the base unit's RJ-45 port or the sensor connection.
2.
Connect the green connector to the DC Input Voltage connector.
3.
Log in to the Gateway as an administrator.
4.
Navigate to the Sensor's page and then to the Digital Voltmeter Settings.
5.
Click on the Calibration button.
6.
After the Calibration page is displayed, click on the Calibrate button. When the sensor has completed the
calibration procedure, it will display "calibration completed."
6