Trane BAYECON353 Series Installation Instructions Manual page 14

0 to 100% low leak economizer - downflow foundation packaged cooling and gas/electric 3 to 5 tons
Hide thumbs Also See for BAYECON353 Series:
Table of Contents

Advertisement

Economizer Controller
Table 4.
Controller menu structure
Menu
Parameter
ECON AVAIL
ECONOMIZING(c)
OCCUPIED(c)
HEAT PUMP
COOL
Y1-IN(c)
COOL
Y1-OUT(c)
COOL
Y2-IN(c)
COOL
Y2-OUT(c)
MA
TEMP(c)
DA TEMP
OA
TEMP(c)
STATUS
OA
HUM(c)
RA
TEMP(c)
RA
HUM(c)
IN CO
2
DCV
STATUS(c)
DAMPER
OUT(c)
ACT
POS(c)
ACT
COUNT(c)
ACTUATOR(c)
14
Parameter
Parameter
Default
Range and
Value
Increment
(c)
NO
NO
NO
N/A
OFF
OFF
OFF
OFF
_ _._ ºF
-40 to 140°F
_ _._ ºF
-40 to 140°F
_ _._ ºF
-40 to 140°F
_ _ %
0 to 100%
_ _._ ºF
0 to 140°F
_ _ %
0 to 100%
(c)
_ _ _ ppm
0 to 2000 ppm
N/A
2.0V
2.0 to 10.0 V
N/A
0 to 100%
N/A
1 to 65,535
OK/Alarm (on
N/A
Alarm menu)
Parameter
Recommended
(a)
(b)
Value
YES/NO
N/A
YES/NO
N/A
YES/NO
N/A
COOL
N/A
HEAT
ON/OFF
N/A
ON/OFF
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ON/OFF
N/A
N/A
N/A
N/A
N/A
Notes
YES = economizing available; the system can use
Outdoor Air for free cooling when required
YES = Outdoor Air being used for 1
YES = OCC signal received from space thermostat
or unitary controller
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC
HEAT PUMP is not available.
Y1-I signal from space thermostat or unitary
controller for cooling stage 1
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
Cool Stage 1 Relay Output to mechanical cooling
(Y1-OUT terminal)
COOL Y2-IN is not available
COOL Y2-OUT is not available
Displays value of measured mixed air from MAT
sensor. Displays --.- if not connected, short, or out-
of-range
DA TEMP is not available
Displays measured value of outdoor air
temperature. Displays --°F if sensor sends invalid
value, if not connected, short or out-of-range
Displays measured value of outdoor humidity from
OA Sylk Bus sensor. Displays --% if not connected,
short, or out- of-range
Displays measured value of return air temperature
from RA Sylk Bus sensor. Displays --°F if sensor
sends invalid value, if not connected, short or out-
of-range
Displays measured value of return air humidity from
RA Sylk Bus sensor. Displays --% if sensor sends
invalid value, if not connected, short or out-of-range
Displays value of measured CO
Invalid if not connected, short or out-of-range. May
be adjusted in Advanced menu by Zero offset and
Span. 0-10 Vdc CO
sensors require CO
2
400 and CO
SPAN to be 1600 in Advanced Setup
2
menu
Displays ON if above setpoint and OFF if below
setpoint, and ONLY if a CO
2
Displays output voltage or position to the damper
(d)
actuator
Displays actual position of actuator
Displays number of times actuator has cycled. 1
Cycle equals the sum of 180° of movement in any
direction
Displays Error if voltage or torque is below actuator
range
st
stage cooling.
from CO
sensor.
2
2
ZERO to be
2
sensor is connected
ACC-SVN203C-EN