Dryer Alarm Table - SPX Hankison GCU Series Instruction Manual

Refrigerated type compressed air dryers
Table of Contents

Advertisement

DRYER ALARM TABLE

Alarm Conditions
Alarm Text
Alarm Trigger
HIGH PRESSURE
High pressure switch open
LOW PRESSURE
Low pressure switch open
COMPRESSOR
Motor protection #1 switch open
HEATER
Heater switch open
DRAIN 1
Drain #1 switch open
DRAIN 2
Drain #2 switch open
SERVICE
Dryer service interval > 0
DRYER
AND Dryer service timer > Dryer service interval
EVAPORATOR
Evaporator temperature sensor out of range
TEMP SENSOR
20
Delay
Monitored
1 Second
Always
3 Minutes
Always
1 Second
Primary
Compressor On
1 Second
Standby
1 Second
Dryer On
1 Second
Dryer On
None
Always
1 Second
Always
Exit Condition
Alarm Action
Manually reset the
Halt compressors
high pressure switch.
De-energize alarm
Alarm reset button
relay #1
pressed
Alarm reset button
Halt compressors
pressed
De-energize alarm
relay #1
Alarm reset button
Halt compressors
pressed
De-energize alarm
relay #1
Alarm reset button
De-energize alarm
pressed
relay #2
Alarm reset button
De-energize alarm
pressed
relay #2
Alarm reset button
De-energize alarm
pressed
relay #2
Alarm reset button
De-energize alarm
pressed
relay #2
Alarm reset button
Halt compressors
pressed
De-energize alarm
relay #1

Advertisement