9. Test run
9.3. Self-check
Refer to the installation manual that comes with each remote controller for details.
RF thermostat is not established.
• Refer to the following tables for details on the check codes. (Wireless remote controller)
[Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
received)
[Output pattern B]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
received)
[Output pattern A] Errors detected by indoor unit
IR wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1
P1
2
P2, P9
3
E6, E7
4
P4
5
P5
6
P6
7
EE
8
P8
9
E4
10
–
11
–
12
Fb
No sound
– –
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
IR wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1
E9
2
UP
3
U3, U4
4
UF
5
U2
6
U1, Ud
7
U5
8
U8
9
U6
10
U7
11
U9, UH
12
–
13
–
14
Others
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does
not come on, there are no error records.
*2 If the beeper sounds three times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)" after the initial two beeps to confirm the self-check start signal was
received, the specified refrigerant address is incorrect.
Beep
Beep
Beep
st
nd
rd
1
2
3
On
On
On
0.5 sec.
0.5 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for "P5")
Beep
st
1
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for "U2")
Wired remote controller
RF thermostat
Check code
Intake sensor error
Pipe (Liquid or 2-phase pipe) sensor error
Indoor/outdoor unit communication error
Drain sensor error
Drain pump error
Freezing/Overheating safeguard operation
Communication error between indoor and outdoor units
Pipe temperature error
Remote controller signal receiving error
–
–
Indoor unit control system error (memory error, etc.)
No corresponding
Wired remote controller
RF thermostat
Check code
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating safeguard operation
Abnormal temperature of heat sink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal
synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
Beep
Beep
Beep
st
nd
th
1
2
n
Off
On
On
On
Approx. 2.5 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
Beep
Beep
Beep
nd
rd
th
2
3
n
On
On
On
0.5 sec.
0.5 sec.
Approx. 2.5 sec.
Symptom
Symptom
· · · Repeated
Beep
1
Off
On
On
Approx. 3 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
For details, check the LED
display of the outdoor controller
board.
Beep
st
nd
· · · Repeated
2
On
0.5 sec.
Remark
Remark
17