Install New Door or Door Adaptor
Remove existing compartment door(s) and remove hinge block using #2 Phillips headed
screw driver.
To install new door follow the instructions below:
Figure 58
To install OEM Door Adaptor Follow the instructions below:
C
De-energize/switch off the LVS section that is to be retrofitted
Open the compartment door that is to be retrofitted.
Rack out the existing legacy AKR breaker from the LVS.
Keep the door open for accessing the door mounting pads placed on the right side
wall in the LVS compartment.
Loosen the screws holding the mounting pads to the compartment frame.
Note that this will provide access for removing the old door from the LVS compartment.
Unpack the new door assembly and mount it on the compartment and secure via
placing the hinges and tightening the screws.
Insert the new retrofitted Emax 2 Retrofill circuit breaker into the compartment and
slide the breaker into the disconnected condition.
Close the new door and secure it to the compartment.
Rack-in the new retrofitted Emax 2 Retrofill circuit breaker.
For ordering the new door depending on door size refer to document
2TSA451008P0000
De-energize/switch off the LVS section that is to be retrofitted.
Open the compartment door that is to be retrofitted.