P R O G R A M S E T T I N G S
10. Press the ENTER button to go to the
connection setting screen (Cnct). The current
setting is shown in the second line. Press the
DOWN ARROW to choose another value. You
can choose 3 EL (element) Wye, 2 Ct del
(Delta) or 2.5 EL Wye.
A
B
C
11. Press the ENTER button to go to the meter
address setting screen (Adr). The meter's
current address is shown in the second line.
To change the setting, press the DOWN
ARROW until the value you want is displayed.
Then press the RIGHT ARROW to move to the
next digit. Repeat until the setting is done.
Valid addresses are from 001 through 247. If
you have the Ethernet option, keep this as 1.
A
B
C
12. Press the ENTER button to go to the meter
baud rate setting screen (bAUd). The meter's
current baud rate is shown in the second line.
Press the DOWN ARROW to choose another
baud rate. You can choose 9600 (choose this
for RS485 connection), 19.2 (19200), 38.4
(38400) or 57.6 (57600). If you have the
Ethernet option, keep this as 57.6.
A
B
C
13. Press the ENTER button to go to the meter
protocol setting screen (Prot). The meter's
current protocol is shown in the second and
third lines. Press the DOWN ARROW to
choose another communication protocol.
You can choose Mod rtU (Modbus RTU;
choose this for RS485 or Ethernet
connection), Mod ASCI (Modbus ASCII)
or dnp (DNP3).
A
B
C
14. Press the ENTER button to go to the scroll
setting screen (SCrL). The current setting is
shown in the second line. Press the DOWN
ARROW to choose another setting. You can
choose YES (the meter readings will scroll on
the display) or no (the meter readings will
not scroll on the display).
A
B
C
15. Press the MENU button twice. You will see
the store settings screen (Stor ALL?) The
default setting is YES. To save the settings
you've made, press the ENTER button. You
will see the confirmation screen (Stor ALL
done) and then the meter resets.
Note: If you do not want to save your settings,
press the RIGHT ARROW. YES changes to NO.
Press the ENTER button.
A
A
B
B
C
C