1.0 INTRODUCTION
These instructions ref er to the above model. Supplementary sheets
are attached if the unit has special options or features. For detailed
specifications, see page 4 or refer to the Data Bulletin. All ADTE CH
instruments are factory calibrated and supplied with a label detailing
the calibration. Adjustments are normally not necessary. A simple
check must be performed to verify calibration before installation to
ensure that it matches the field requirement.
2.0 GENERAL DESCRIPTION
The TCT-327-MOD transmitter accepts a type S thermocouple input
and provides a linearized and isolated
temperature at a rate of 500 samples per second (130 Hz
bandwidth). Calibration is extremely easy with Adtech's Smart
technology. Simply input your zero value, touch a button,
Touch®
input your span value and touch another button, and the unit is
calibrated.
The isolated output resolution is 12 bits and provides 0-5 Vdc.Other
voltage or current output signals are available (see table 1 page 3)
Isolation is 600 volts ac or 1000 volts de from the input to the output
/ power supply. Power requirements are 15 to 42 Vdc at 40 ma
maximum.
The primary features are:
Wide range - covers the full range of the ISA standard type S
thermocouple.
Output setup is via plug in jumpers.
High accuracy, input resolution of 0.6µv for 0.1 °C resolution.
High speed (500 samples per second) linearized conversion.
RFI resistant.
NO INTERACTION of zero and span controls.
Adtech Smart Touch® calibration.
Small size - DIN mounting package (1 "w x 3.1 "h x 3.6"d).
Options for NEMA 4 and NEMA 7 housings, SNAP TRAK and
surface mounting.
3.0 INSTALLATION
Electrical Connections
The wire used to connect the instrument to the control system 1/0
should be a twisted pair(s) and sized according to normal practice.
Shielded cable is not normally necessary (if used, the shield must
be grounded at the input negative of the ADTECH instrument and
left floating at the sensor).
TCT-327-MOD
Inc.
Hi-Speed type S TC Isolated Transmitter
Instruction Manual
Six position compression terminal blocks are provided for 1/0 and
power connection. A housing ground terminal is not required due
to non-metallic housing.
Controls
Instrument controls consist of the following:
output representing
4.0
These instruments are electronic and require no maintenance
except periodic cleaning and calibration verification. If the unit
appears to be mis-operating it should be checked per sections 6.0
and 7.0. MOST problems are traced to field wiring and
associated circuits.
instrument, proceed to sections 6.0 and 7.0.
5.0 CONNECTIONS
Standard connections are shown below and on the instrument face
plate, Data Bulletin or on attached supplementary sheets.
-1-
• 8 position switch for input configuration and calibration
options.
I
• Jumper for zero based
elevated output.
• Output zero and span pots.
• Input zero and span push buttons (Adtech
MAINTENANCE
If the problem appears to be with the
(+)------
Type S TC Input
------.1
(-)
1.�:1.•1,•
,..,.Jto
_ l..,,
'-
l
!•
l
t
input
@
I
SPAN
j
j
INCN.
J
t::.:\
ZERO
{
I
®
SPAN
&:\
S T ATUS
'
� ZERO
\
l�
l
ADTECH
t
TCT-327
SPAN@
}
OU T CN.
I
ZERO@
;
,
- +
+V;
/
ii:,,J,
• .
I
Common
(-)------
0 to 5Vdc Output
(+)------
...... -----(+)
Smart Touch®)
I
or
Power 15 to
42VDC
190-A-000097 Rev. A
(8/ 99)

Advertisement

loading

Summary of Contents for Adtech TCT-327-MOD

  • Page 1 • . should be a twisted pair(s) and sized according to normal practice. Shielded cable is not normally necessary (if used, the shield must Common be grounded at the input negative of the ADTECH instrument and Power 15 to (-)------ 42VDC left floating at the sensor).
  • Page 2 6.0 CONFIGURATION 7.0 FIELD TROUBLE SHOOTING GUIDE All ADTECH units are factory calibrated per P.O. instructions. This section offers a simple, first level trouble-shooting aid for an Usually, a complete recalibration is not required uf'lless you want to apparent instrument malfunction.
  • Page 3 8.0 TABLES Output Configuration Jumpers Configuration Switch SW3 Switch Output PCB Input PCB Function (Small Board) (Large Board) Position Output Downscale burnout 4-20mA Upscale burnout 0·20mA No Linearization 0-10mA Linearized 0-1mA Normal Operation 1-5V Output the zero Value 0-5V Normal Operation 0-10V Output the span Value Table 1...
  • Page 4 9.0 SPECIFICATIONS INPUT/OUTPUT Temperature Range: ° ° ° ° to 185 F (-31 to 85 ° INPUT SIGNAL operating; -40 ° to 200 ° F (-40 ° to 93 C) storage Type S thermocouple, standard ISA calibration from -50 to Power Supply Effect: ±...