Download Print this page
Intermatic EMKB Installation Manual
Intermatic EMKB Installation Manual

Intermatic EMKB Installation Manual

Lighting control equipment

Advertisement

Quick Links

lIghtIng COntROl eQuIPMent
InstallIng the eMKB
The EMKB is a 100% digital momentary switch, avail-
able with 1 to 6 buttons per switch. It can be mounted
in any standard switch box with a decorator style switch
plate. This switch is NOT pre-programmed and must be
addressed and programmed in the field.
Placement and Wiring
1.
Connect to the digital lighting control bus using Cat. 5
cable with RJ45 connectors. Note all items on the bus
must be "daisy chained" and the beginning and end
items on the bus must have a terminator. If this is being
added to the bus in the middle this is not a problem. If
added at the end of the bus make sure the terminator
is removed from the previously last item to the new last
item on the bus.
If the ON LINE LED is not flashing re-check connections
2.
and crimps.
Address and define per instructions in the EM1400
3.
Quick Hook-Up Guide and System and Software Start-
Up Manual. This would be defined as a (Number of
Butons) button switch in the "PANEL SWITCH TYPES"
Menu.
4.
Program the switch to control the appropriate loads. The
Switch will be shown in the PROGRAM SWITCH menu.
For more complete details on programming switches
see the O & M Manual.
InteRMatIC InCORPORateD • http://www.intermatic.com
eMKB
DIgItal sWItCh
InstallatIOn
guIDe
EMKD4 Shown

Advertisement

loading