6.2.5.9 Password Set-up
The password for 'Detail Info' and 'Technical Set' can be reset here.
Password:
1100
Confirm:
1100
Press ENT to move the cursor, press UP/DOWN to select a number for a digit
selected, and press ENT to confirm the setup after the last digit has been set
up. Press ESC to return to previous menu.
6.2.5.10 Factory Reset
This function is designed to restore factory defaults.
YES=ENT
EXIT=ESC
Are You Sure ?
6.2.5.11 Adjust Total E
The total energy generated may be cleared or changed after maintenance or
translocation, and the previous data can be restored with this function. The
total energy generated can be adjusted here.
TOTAL
ENERGY
5700000 KWh
6.2.5.12 Reset Total E
The total energy generated record can be cleared here, and after clearing, the
energy generation record will be zero.
YES=ENT
EXIT=ESC
Are You Sure?
Press ENT to clear the energy generation history and press ESC to cancel the
previous operation.
6.2.5.13 Inverter On/Off
This function is to control the grid connection or disconnection of inverters.
Inverter
ON/OFF
ON
41
Press UP/DOWN to scroll the menu, press ENT to perform the selection, and
press ESC to return to the previous menu.
6.2.5.14 Export Limit
->Soft Limit
->Hard Limit
->Detection Mode
The inverter's export limit can be achieved together with external devices
such as a CT or meter. There are two types of limit, soft limit and hard limit.
The soft limit means that the limit is controlled by software, and hard limit
means that if the generation exceeds the limit, the inverter will stop working.
Under the detection mode menu, you can choose CT mode or meter mode.
For the normal working of inverters, please use the soft limit only. The hard
limit is used only by compulsory requirement of local grid companies.

7. Maintenance and Troubleshooting

7.1 General Maintenance
The Inverters do not need regular maintenance and just ensure that they are
free of dust, foliage and other dirt.
NOTE:
The use of cleaning agents may damage the machine and