2.6 Installation Type (e) – DPF Housing
A standard DPF Housing design is used for stationary engines and gensets. Please follow the instruction below
to install the standard DPF Housing for a genset/stationary engine.
1) The DPF Housing is to be mounted upstream of the original equipment muffler.
2) Determine a suitable horizontal space as close as possible to the engine exhaust outlet.
3) Allow adequate space (~30" (762 mm)) for loading and unloading the individual filter units.
4) Secure the DPF Housing feet to a concrete foundation or structural steel.
4) Use a flex to isolate the DPF Housing from vibrations from the engine or exhaust stream.
5) Four ½" test ports are provided to perform manual backpressure checks or emissions testing.
Figure 2.5 – Example of a DCF2X3X3 MINE-X SOOTFILTER
®
DCL MINE-X SOOTFILTER
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
LAST REVISED: SEPTEMBER 2009
MINE-X SOOTFILTER
®
DPF Housing