Hitachi RAC-35WXE Service Manual page 8

Hide thumbs Also See for RAC-35WXE:
Table of Contents

Advertisement

Figure showing the installation of lndoor and Outdoor unit
MODEL RAC-50WXE
above 200mm
above 300mm
above 700mm
above 150mm
give clearance
as wide as
possible
The connection of insulated drain
above
hose.
200mm
Please use insulated drain hose for
the indoor piping (commercial
product)
8
The refrigerating machine oil is
easily affected by moisture. Use
caution to prevent water from
entering the cycle.
The difference in height between
the indoor and outdoor unit
should be kept below 10m.
The connecting pipe, no matter
big or small, should all be
insulated with insulation pipe and
then wrapped with vinyl tape.
(The insulator will deteriorate if
it is not wrapped with tape).
Inner diameter 16mm

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rac-25wxeRac-50wxe

Table of Contents