Ld0.Pemmtr1 Power Measurement And Accumulated Power Values; Dr.rdre1 Disturbance Recorder Values; Ld0.Rescmmxu1 Residual Current (1); Ld0.Resvmmxu1 Residual Voltage (1) - ABB REM615 Manual

Motor protection and control dnp3 point list manual
Hide thumbs Also See for REM615:
Table of Contents

Advertisement

Section 2
DNP3 data mappings
2.3.3.17
Table 91:

LD0.PEMMTR1 Power measurement and accumulated power values

IEC 61850 name
LD0.PEMMTR1
.DmdVArh.actVal
.DmdWh.actVal
.SupVArh.actVal
.SupWh.actVal
.TotPF.instMag
.TotW.instMag
.TotVA.instMag
.TotVAr.instMag
2.3.3.18
Table 92:

DR.RDRE1 Disturbance recorder values

IEC 61850 name
DR.RDRE1
.FltNum.stVal
.MemUsed.stVal
2.3.3.19
Table 93:

LD0.RESCMMXU1 Residual current (1)

IEC 61850 name
LD0.RESCMMXU1
.A.res.instCVal.mag
2.3.3.20
Table 94:

LD0.RESVMMXU1 Residual voltage (1)

IEC 61850 name
LD0.RESVMMXU1
.PhV.res.instCVal.mag
36
LD0.PEMMTR1 Power measurement and accumulated power values
SA name
Description
ER_RV_ACM
Forward reactive energy
EA_RV_ACM
Forward active energy
ER_FWD_ACM
Reverse reactive energy
EA_FWD_ACM
Reverse active energy
PF_INST
Average power factor
P_INST
Active power
S_INST
Apparent power
Q_INST
Reactive power
DR.RDRE1 Disturbance recorder values
SA name
Description
-
Number of recordings
-
Rec. memory used
LD0.RESCMMXU1 Residual current (1)
SA name
Description
I0_INST
Residual current
LD0.RESVMMXU1 Residual voltage (1)
SA name
Description
U0_INST
Residual voltage
Values
S
Arg 1,2,3,4
0...1e10
R
0,1E10,0,1E10
0...1e10
R
0,1E10,0,1E10
0...1e10
R
0,1E10,0,1E10
0...1e10
R
0,1E10,0,1E10
-1...1
R
-1,1,-100,100
0...999999
R
0,999999,0,999999
0...999999
R
0,999999,0,999999
0...999999
R
0,999999,0,999999
Values
S
Arg 1,2,3,4
0...65535
R
0,65535,0,65535
0...100 [%]
R
0,100,0,100
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
Values
S
Arg 1,2,3,4
0.00..4.00
[xUn]
R
0,4,0,400
1MRS756880 C
REM615
Point List Manual

Advertisement

Table of Contents
loading

Table of Contents