SEC CELLYTE 6-12TLG Installation And Operating Instructions Manual

Stationary gel batteries

Advertisement

Quick Links

CELLYTE 6-12TLG
STATIONARY GEL BATTERIES
INSTALLATION and OPERATING
INSTRUCTIONS
NON-SPILLABLE by DOT
(Department of Transportation)
ICAO (International Commercial Airline Organization)
and IATA (International Airline Transport Assocaiation)
Supplied Worldwide by :
SEC Industrial Battery Company
Last Revised May 2011
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CELLYTE 6-12TLG and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SEC CELLYTE 6-12TLG

  • Page 1 CELLYTE 6-12TLG STATIONARY GEL BATTERIES INSTALLATION and OPERATING INSTRUCTIONS NON-SPILLABLE by DOT (Department of Transportation) ICAO (International Commercial Airline Organization) and IATA (International Airline Transport Assocaiation) Supplied Worldwide by : SEC Industrial Battery Company Last Revised May 2011...
  • Page 2: Table Of Contents

    Maintenance Records 5.1.4 Floor Loading Seismic Considerations CAPACITY TESTING Installation - Cabinets General Installation - Racks Test Procedures 5.4.1 Existing racks Discharge Test Notes 5.4.2 New racks 5.4.3 Installation 10.0 Battery Maintenance Register 11.0 SEC Technical Support 12.0 SEC Battery Report...
  • Page 3: General Information

    Sulphuric Acid SECTION 3 - RECEIPT OF EQUIPMENT The CELLYTE 6-12TLG Bloc is a lead acid battery and Delivery Inspection contains Sulphuric acid in diluted form. Because the electrolyte is immobilized, in the event of case rupture, Immediately upon delivery, inspect the batteries for no liquid acid will leak or run from the battery.
  • Page 4: Storage

    20ºC will result in loss of battery operation life. For every 8ºC rise in battery temperature above 20 ºC, the life of 5.1.4 Floor Loading the battery will be cut in half. For example, the CELLYTE 6-12TLG Bloc battery is designed for a 10 Before installing batteries, should year float service life at 20ºC.
  • Page 5: Seismic Considerations

    Seismic Considerations. that all tools are insulated with vinyl electrical tape to prevent shorting. Do not reach or lean across CELLYTE 6-12TLG Bloc batteries are capable of with batteries on step racks. Remember, hazardous standing seismic events of UBC Zone 4 magnitude when voltages are present.
  • Page 6: Voltage Checks

    Calculate At voltages below 2.29 VPC adequate equalization will the average Bloc voltage and use this value to refigure not be obtained. Contact your SEC representative for the string voltage. If the recalculated and measured...
  • Page 7: Maximum Charge Current

    Section 7 - STORAGE The maximum charge currents are : When installed CELLYTE 6-12TLG Bloc Maximum Charge Rates for CELLYTE 6 &12TLG Bloc TYPE AMPS batteries will not be used (floated) for a period of time, 6TLG-130 18.6...
  • Page 8: General Records

    multiplying the load current by the number of hours of Do not use any solvents or strong cleaners on or around run time. The actual AH capacity can be compared to the batteries. A dry brush may be used to remove any the rated AH capacity to determine percentage capacity.
  • Page 9: Discharge Test Notes

    (13) Keep a copy of all the test data with the battery records. Discharge Test Notes: (1) CELLYTE 6-12TLG Bloc batteries are shipped at about 90% capacity, full capacity will be achieved after 10 to 15 deep cycles or 3 months on float charge.
  • Page 10: Battery Maintenance Register

    SEC BATTERY MAINTENANCE REGISTER Maintenance Description Date Industrial Battery Co. Industrial Battery Co.
  • Page 11: Sec Technical Support

    11 TECHNICAL SUPPORT SEC is always ready to assist you in your installation and operation of SEC CELLYTE 6- 12TLG batteries. If you have any questions on any portion of this manual, please do not hesitate to call or fax any of our offices listed below and request assistance.
  • Page 12: Sec Battery Report

    SEC BATTERY REPORT Installed by: Representative: Operating Company: Date: Time: Address/Location: Battery Information Type of Battery: No. of Cells/String: String Float Voltage: Installation Date: No. of Strings/Battery: Float Voltage/ Cell: Battery Charge Current: Battery Code: Float Current: Charging Equipment: Ambient Temperature:...