Standalone & integrated intelligent
Hide thumbs Also See for PSU200:

Advertisement

INSTALLATION
MANUAL
PSU200 & PS200XP
Standalone & Integrated intelligent
Power Supply Units
INS314-8

Advertisement

loading
Need help?

Need help?

Do you have a question about the PSU200 and is the answer not in the manual?

Questions and answers

Summary of Contents for Texecom PSU200

  • Page 1 INSTALLATION MANUAL PSU200 & PS200XP Standalone & Integrated intelligent Power Supply Units INS314-8...
  • Page 2 15-06-2022 • Changes to battery ratings tables as per PCR01618...
  • Page 3: Table Of Contents

    Content 1.0 Introduction ..........................2.0 PCB Layout and Terminals ....................3.0 Standby Battery ........................4.0 Installation ..........................5.0 Wiring Diagrams ........................6.0 Specifications ........................7.0 Standards ..........................8.0 Warranty ..........................INS314-8 3/17...
  • Page 4: Introduction

    1.0 Introduction The Premier Elite PSU200 is a standalone intelligent 2.5 Amp power supply. The Premier Elite PSU200XP is a PSU200 combined with a Premier Elite 8XP zone expander to create a fully monitored power supply unit via the control panel network.
  • Page 5 INS314-8 5/17...
  • Page 6: Pcb Layout And Terminals

    2.0 PCB Layout and Terminals The figure below shows the PCB layout of the PSU200 and PSU200XP: Texecom Power Supply Connection. Connector to case tamper switch. Power LED Communication port (for connection to 8XP zone expander). Battery 1 charge current selector (0.75A or 0.30A).
  • Page 7 Battery 2 charge current selector (0.75A or 0.30A). Battery load test options. 12V supply output. External load for battery load test. Not Used Normally closed tamper output. Number of batteries connected. 12V output protection fuse (1.6A). Battery 1 and 2 connections. Battery kick start switch.
  • Page 8: Standby Battery

    PCB via a jumper plug JP2. When installing a PSU200 the two tamper connections terminals should be connected to the tamper or 24hour zone of the alarm control panel. The tamper connections are not required for the PSU200XP as the tamper status is detected through the communication port.
  • Page 9 (maximum continuous current) for the required standby period: PSU200 Rated Output (Amps) Battery Arrangement Battery Charge 1 x 7Ah 0.3A 0.53A 0.24A 0.18A 0.071A 2 x 7Ah 0.3A 1.1A 0.53A 0.42A 0.18A 0.3A 1.37A 0.66A 0.52A 0.23A 1 x 17Ah 0.75A...
  • Page 10 Battery Monitoring Each battery is monitored independently, therefore, the number of batteries connected to the PSU200/PSU200XP must be set using JP8. If JP8 is set to “1 Battery” then battery 2 is not monitored. The following conditions are monitored: INS314-8 10/17...
  • Page 11 If either battery is disconnected during this test a battery fault is generated. Load: The PSU200 tests the standby batteries every 24 hours by allowing the batteries to power the PSU and connected devices for a period of 10 seconds.
  • Page 12: Installation

    B only = PSU Load + External Load (if any) + 500mA C only = PSU Load + External Load (if any) + 500mA B + C = PSU Load + External Load (if any) + 1A No jumpers fitted is the same as fitting jumper A, ie PSU Load + External Load (if any) (see items - and 9 of Figure...
  • Page 13: Wiring Diagrams

    5.0 Wiring Diagrams PSU200XP Connected to Premier Elite Control Panel For a list of supported control panels, see Introduction. INS314-8 13/17...
  • Page 14 The PSU200 can be fully monitored by other makes of control panels, by using the fault and tamper terminals. The zones on the control panel will need to be programmed for PSU monitoring functionality. Please consult the manufacturer’s instructions in order to ascertain whether the control panel supports these zone types.
  • Page 15: Specifications

    Minimum energy level 100% (to meet the backup periods specified in this of the SD in its charged manual) state Location The PSU200 should be mounted within the supervised premises. Operating temperature -10°C to +50°C Maximum humidity 95% non-condensing Dimensions...
  • Page 16: Standards

    Texecom cannot accept responsibility or liability for any damages whatsoever based on a claim that the Premier Elite PSU200 or PSU200XP failed to function correctly. Due to our policy of continuous improvement Texecom reserve the right to change specification...
  • Page 17 Premier & Premier Elite are trademarks of Texecom Ltd. INS314-8 17/17...