Pts PTS90423 Series Installation Manual

Compact 120v ac power distribution panel 60a main breaker, with external rotary disconnect switch suitable for use as service equipment small cell, pico, micro, cran or macro. maximum 6 ul489 breaker positions with single spd. maximum 5 ul489 breaker posi

Advertisement

Quick Links

PTS90423 Series
120V AC Power Distribution Panel
60A Main Breaker,
with External Rotary Disconnect Switch
Suitable for Use as Service Equipment
Small Cell, Pico, Micro, CRAN or Macro
INSTALLATION GUIDE
Compact 120V AC Power Distribution Load Center
60AMP Main Breaker with External Rotary Disconnect Switch
Single SPD (L-G) per Leg or Dual SPD (L-N) per Leg, (N-PE)
PTS90423 - Maximum 6 UL489 Breaker Positions with Single SPD
PTS90423 - Maximum 5 UL489 Breaker Positions with Dual SPD
Scan the QR code above to link to current document or click the link below:
All Rights Reserved, 2018
www.pactechsol.com
www.pactechsol.com
888-820-3508
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PTS90423 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Pts PTS90423 Series

  • Page 1 PTS90423 Series 120V AC Power Distribution Panel 60A Main Breaker, with External Rotary Disconnect Switch Suitable for Use as Service Equipment Small Cell, Pico, Micro, CRAN or Macro INSTALLATION GUIDE Compact 120V AC Power Distribution Load Center 60AMP Main Breaker with External Rotary Disconnect Switch...
  • Page 2: Table Of Contents

    Distribution Breakers ........................8 Optional Surge Protection Device…………………………………………………………….....8 2.4 Suitable for Use as Service Equipment............... .…….…..8 3.0 Inspecting and Unpacking of PTS90423 Series Panels ..............9 3.1 Steps to Inspect and Remove……………………………………………………………………….…9 4.0 Mounting............................9 4.1 Mounting Bracket..........................9 4.2 Mounting to Pole, Stanchion or Round Surfaces ................10...
  • Page 3: Model Overview

    AC Power Distribution Load Centers Installation Guide 1.0 Model Overview The PTS90423 Series of Small Cell AC Power Distribution Load Centers provides a custom factory fully assembled load center for Small Cell and CRAN deployments. The PTS90423 Series products are: Suitable for Use as Service Equipment.
  • Page 4 PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide PTS90423 Outline Drawing Example with Dual SPD and 5 Load Positions Figure 2: Dimensional Drawings Caution: Installation shall be completed per all NEC and Local Codes. Do not install PTS90423 Systems before reading and understanding all specifications and installation guides provided.
  • Page 5: Specifications

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 1.1 Specifications Electrical Operating Voltage 120VAC Main Breaker 60Amp MAX Distribution Breakers Max of (6) UL489 Breakers 0-20Amp Power Input Wire Size #14 - #4 awg Cu - Al...
  • Page 6: Breaker Specifications

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 1.2 Breaker Specifications Breaker Specifications PTS P/N Description PT-KM1N-07A UL489A DIN rail Breaker, 07 AMP PT-KM1N-10A UL489A DIN rail Breaker, 10 AMP PT-KM1N-12A UL489A DIN rail Breaker, 12 AMP...
  • Page 7: Wiring Diagrams

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 1.3 Wiring Diagrams PTS90423 Wiring Diagram Suitable for Use as Service Equipment NEUTRAL to GROUND BOND Require when using for SERVICE EQUIPMENT Drawing above shows equipped with Neutral to Ground Bond Required when Using for Service Equipment.
  • Page 8: Application

    The PTS90423 is a compact AC Load Centers designed for Small Cell and CRAN Deployments where distribution of AC power is required. The PTS90423 Series of compact AC Load Centers can also be used for AC Power Distribution applications where limited space exists, excluding the ability to use a larger load center.
  • Page 9: Inspecting And Unpacking Of Pts90423 Series Panels

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 3.0 Inspecting and Unpacking of PTS90423 Series Load Centers 3.0.1 Inspect the packaging for obvious signs of rough handling and/or external damage. 3.0.2 Review Installation Guide. 3.0.3 Remove from plastic packaging.
  • Page 10: Mounting To Pole, Stanchion Or Round Surfaces

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 4.2 Mounting enclosure to Pole, Stanchion or Round Surfaces 4.2.1 Customer is responsible to identify suitable location for mounting 4.2.2 Install Pole Straps and tighten per specifications -or - 4.2.3 Mark and drill anchors locations using template provided.
  • Page 11: Mounting To Flat Surfaces

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 4.3 Mounting enclosure on flat surfaces 4.3.1 Customer is responsible to identify suitable location for mounting. 4.3.2 Mark and drill anchors or clips to secure enclosure to surface.
  • Page 12: Accessing Dead Front Plate And Breakers

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 5.1 Removing Dead Front Access Plate 5.1.1 Locate Dead Front Access Plate set screw and remove 5.1.2 Set aside for reuse. 5.1.3 Review Equipment Ground Connection Points 5.1.4 Review Neutral Connection points 5.2 Wiring Ground Connections...
  • Page 13: Wiring Load Connections

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 5.3 Wiring Service and Load Connections 5.3.1 Wiring to be done in accordance with NEC and Local Jurisdictions Code. 5.3.2 Wire the Service Ground to the internal ground bar 5.3.3...
  • Page 14 PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide Figure 6: Standard Wiring Practice Example Caution: Installation shall be completed per all NEC and Local Codes. Do not install PTS90423 Systems before reading and understanding all specifications and installation guides provided.
  • Page 15: Re-Installing Dead Front Access Plate

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 5.4 Re-Intalling the Dead Front Access Plate 5.4.1 Reinstall the Dead Front Access Plate and ensure that it is seated correctly. 5.4.2 Reinstall the Dead Front Access Plate set screw and tighten.
  • Page 16: Labeling The Breakers

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 5.5 Labeling the Breakers 5.5.1 If installed as Service Equipment, apply the "SERVICE DISCONNECT" label at the primary breaker positions If installed as Branch Equipment, apply the "MAIN DISCONNECT" label at the 5.5.2...
  • Page 17: Installation Review

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 6.0 Installation Review Inspect the installation, verifying that all is in accordance with this document, NEC, and local Codes. Caution: Installation shall be completed per all NEC and Local Codes. Do not install PTS90423 Systems before reading and understanding all specifications and installation guides provided.
  • Page 18: Document And Revision Control

    PTS 90423 Series Small Cell AC Power Distribution Load Centers Installation Guide 7.0 Document and Revision Control Author Tom Cooleen Date 06/05/2018 File Location www.pactechsol.com Revision Control Issue Number Date 09/05/2018 Description PTS90423 Series Installation Guide Prime Contact 1 Name...

Table of Contents