Fault Output - Bosch Thermotechnik MU 100 Installation Instructions Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 16
Commissioning
Meu item
Pump control
Max. value
Max. flow temp
control
Maximum range
Proportional range
dT set value
Proportional factor
dT control
Integral factor
Differential factor
Max. differential
Maximum range
Max diff control
Proportional range
Ramp
Heat source control (setpoint value)
Config mode 0-10V
Input value f. off
Input value f. max.
Max. temp. set v.
Min. temp. set v.
Table 9
Menu MU 100 (for CW 400/RC310 from NF74.xx)
4.4

Fault output

The fault outputs (OE1-75 and OP0 in coding positions 3-5) are
only activated following a delay 10 of minutes after the fault has
occurred. If no faults are present, the fault output is deleted
immediately. Faults, which disappear within the delay time of
10 minutes, are not displayed on the fault output.
26
Settings/adjustment range
85 ... 100 °C
1 ... 4 ... 20 K
1 ... 5 ... 20 K
off | 0.5 ... 2.5 ... 20 K
1 ... 10 ... 100 K
0 ... 60 ... 600 s
0 ... 150 s
25 ... 40 ... 85 K
1 ... 10 ... 20 K
1 ... 5 ... 20 K
off | 1 ... 5 ... 20 %/s
Temp. | Output
0 ... 10 V
0 ... 10 V
0 ... 90 ... 100 °C
0 ... 20 ... 100 °C
Remark/restriction
Enter maximum flow temperature
Enter width of max. range
Enter width of proportional range
Enter temperature differential set value
Set proportional factor for controller
Set integral factor for control unit
Set differential factor for control unit
Set maximum temperature differential
Enter width of max. range
Enter width of proportional range
Enter ramp for pump modulation
Boiler control via temperature or output?
Switch off boiler with voltage
Boiler at max. output with voltage
Set max. set temperature
Set min. set temperature
MU 100 – 6721831604 (2021/01)