CABLE CONNECTION METHOD

Fig. 1: Wago connectors
CABLING RECOMMENDATIONS FOR THE Rx100 INTERFACE.
Although BBV do not specify any particular type, manufacturer or supplier of cables, the following
ESD Electronic Services (01279 626777) cables have been used successfully for production and
testing:
ESD Part Number:
0222586G
(100 m)
020966D
(100 m)
0140467H
(100 m)
Installation Manual – Rx100 Interface Edition 1.5
The WAGO PCB terminal block is a simple-to-use method of
attaching cables to PCBs quickly and easily. Prepare cables
as follows:
Use only cable between 0.08 and 2.5 mm²
Strip the cable to a length of 5 to 6 mm (0.23 in)
The correct method of attachment is as follows:
1. Press down the relevant terminal block lever with a
suitable screwdriver;
2. Insert wire;
3. Remove screwdriver.
The procedure for detaching wires is the reverse of the 3
attachment steps, ensuring that power is disconnected
before starting.
Description:
Co-Ax Cable (Minimum Specification)
RG59B/U ESD radio frequency coax cable to BS2316 and MIL-C-17
1/0.58mm copper-covered
dielectric, bare copper wire braid and PVC sheath
Characteristic impedance: 75 Ohm
Capacitance: 22pF/ft
Orange-Coloured Lighting Output Power Cable (1000 w)
3183Y PVC-insulated, 3-core cable
²
1.25mm
40/0.2mm annealed copper conductor
Current rating: 13 amp
20mA Twisted Pair Cable (Minimum Specification)
British Telecom spec CW 1308
2-core 1/0.5mm PVC-insulated
Maximum conductor resistance at 20 degrees Celsius: 97.8 ohms/km
steel wire conductor with solid polythene
March 2001