Ld0.Defhpdef1 Directional Earth-Fault Protection - High Stage 1; Ld0.Deflpdef1 Directional Earth-Fault Protection - Low Stage 1; Ld0.Cmmxu1 Phase Currents (1) Limit Supervision; Ld0.Rescmmxu1 Residual Current (1) Limit Supervision - ABB 620 Series Manual

Motor protection and contro
Hide thumbs Also See for 620 Series:
Table of Contents

Advertisement

Section 2
IEC 60870-5-103 data mappings
2.3.76
Table 79:

LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1

IEC 61850 name
SA name
LD0.DEFHPTOC1
.Str.general
START
.Op.general
OPERATE
2.3.77
Table 80:

LD0.DEFLPDEF1 Directional earth-fault protection - low stage 1

IEC 61850 name
SA name
LD0.DEFLPTOC1
.Str.general
START
.Op.general
OPERATE
2.3.78
Table 81:

LD0.CMMXU1 Phase currents (1) limit supervision

IEC 61850 name
SA name
LD0.CMMXU1
.HiAlm.stVal
HIGH_ALARM
.HiWrn.stVal
HIGH_WARN
.LoWrn.stVal
LOW_WARN
.LoAlm.stVal
LOW_ALARM
2.3.79
Table 82:

LD0.RESCMMXU1 Residual current (1) limit supervision

IEC 61850 name
SA name
LD0.RESCMMXU1
.HiAlm.stVal
HIGH_ALARM
.HiWrn.stVal
HIGH_WARN
42
LD0.DEFHPDEF1 Directional earth-fault protection - high
stage 1
Description
High (1) stage
-start
-operate
LD0.DEFLPDEF1 Directional earth-fault protection - low
stage 1
Description
Low (1) stage
-start
-operate
LD0.CMMXU1 Phase currents (1) limit supervision
Description
High alarm
High warning
Low warning
Low alarm
LD0.RESCMMXU1 Residual current (1) limit supervision
Description
High alarm
High warning
DPI value
FUN
10=Start
163
10=Operate
163
DPI value
FUN
10=Start
163
10=Operate
163
DPI value
FUN
10=Alarm
210
10=Warning
210
10=Warning
210
10=Alarm
210
DPI value
FUN
10=Alarm
210
10=Warning
210
1MRS757657 A
INF
U
ASDU
I
C
96
1
2
1
1
98
1
2
0
1
INF
U
ASDU
I
C
84
1
2
1
1
90
1
2
0
1
INF
U
ASDU
I
C
1
1
1
1
1
2
1
1
1
1
3
1
1
1
1
4
1
1
1
1
INF
U
ASDU
I
C
11
0
1
1
1
12
0
1
1
1
REM620
Point List Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rem620

Table of Contents