5.2 Steps for dismantling the modules
 Remove the removable terminals with wiring and the end clips.
 If there are several modules, slide the modules away from each other
individually in the direction of the arrow until the side plug connection is
separated.
 Press the module downwards at the rear (1)) and remove it from the
DIN rail in the direction of the arrow while keeping it pressed down (2)).
6 Electrical installation
De-energize the entire system!
Mettez le système entièrement hors tension !
The system could start up unexpectedly while you are
ATTENTION
connecting the devices.
Le système pourrait être mis en marche par inadvertance
pendant qu'on connecte les dispositifs.
Observe the relevant safety standards!
Observez les normes de sécurité pertinentes!
All safety related parts of the installation (cabling,
connected sensors and actuators, configuration settings,
EDM) must be according to the relevant safety standards
(e.g. IEC 62061 or EN/ISO 13849-1).
Tout matériel ou logiciel ayant des implications de sécurité
(câblage, capteurs et actionneurs à raccorder,
paramétrages de configuration, EDM) doivent être
conformes aux normes de sécurité applicables (par
exemple, IEC 62061 ou EN/ISO 13849-1).
 The MELSEC-WS safety controller fulfils the EMC requirements in
accordance with the basic specification IEC 61000-6-2 for industrial use.
 Carry out the electrical installation in accordance with EN 60204-1
 To ensure full electromagnetic compatibility (EMC), the DIN rail has to
be connected to functional earth (FE).
 The voltage supply of the devices must be capable of buffering brief
mains voltage failures of 20ms as specified in IEC 60204-1.
 The voltage supply has to fulfil the regulations for extra-low voltages
with safe separation (SELV, PELV) in accordance with IEC 60664 and
EN 50178 (equipment of electrical power installation with electronic
devices).
 You must connect all the modules of the MELSEC-WS safety controller,
the connected protective devices as well as the voltage supply/ies with
the same 0VDC (GND).
 All connected pick-ups and downstream controllers as well as wiring
and installation have to fulfil the required safety characteristics.
 If a module is replaced the correct terminal assignment has to be
guaranteed, for example by labelling or suitable cable routing.
 For further information that is to be taken into consideration when the
MELSEC-WS safety controller is used, refer to the "Safety Controller
User's Manual" and "Safety Controller Setting and Monitoring Tool
Operating Manual".
7 Configuration and commissioning
Do not commission without a check by qualified
safety personnel!
Ne pas procéder à la mise en service sans qu'un
ATTENTION
personnel de sécurité qualifié ait effectué un
contrôle.
Before initial commissioning of a system using a
MELSEC-WS safety controller, it must be checked and
released by qualified safety personnel. Document the
result of the safety check.
La première mise en service d'un système utilisant un
contrôleur de sécurité MELSEC-WS ne doit être
effectuée qu'après contrôle et sur autorisation délivrée
par un personnel qualifié. Les résultats du contrôle de
sécurité doivent être dûment documentés et suivis.
The MELSEC-WS safety controller can be configured by the Setting and
Monitoring Tool connected to the RS-232 interface or USB interface (only
WS0-CPU3 module) of a CPU module, or the port of an Ethernet interface
module.
Note  The Setting and Monitoring Tool is required to configure and
commission the MELSEC-WS safety controller.
 The system configuration of the complete MELSEC-WS safety
controller is stored in the memory plug. The system does not
have to be reconfigured when a module is replaced.
 For the diagnostics after module replacement with the higher
version (for instance, upgraded from V1.11.0 to V2.01.0), the
Setting and Monitoring Tool version 1.7.0 is required.
8 Technical data
Safety-related parameters
This information relates to an ambient temperature of +40°C, which is
normally used for the statistical calculation of the values.
WS0-CPU0
WS0-CPU1/3
Safety Integrity Level
SIL3 (IEC 61508)
SIL claim limit
SILCL3 (IEC 62061)
Category
Category 4 (EN/ISO 13849-1)
Performance Level
PLe (EN/ISO 13849-1)
PFHd
1.07 × 10
-9
1.69 × 10
-9
CPU1: -
PFHd for Flexi Line
-
*1
station
CPU3: 0.40 × 10
T
(mission time)
20 years (EN/ISO 13849-1)
M
*1 Applies for a CPU module WS0-CPU3 that is used exclusively for
routing information via Flexi Line.
General data
WS0-CPU0
WS0-CPU1/3
Protection class
III (IEC 61140)
Enclosure rating
IP20 (IEC 60529)
Ambient temperature in
operation
-25 ... +55°C
Température ambiante
-25 à +55°C
de fonctionnement
Storage temperature
-25 ... +70°C
Humidity
10% ... 95%, non-condensing
55°C, 95% relative humidity (IEC 61131-2),
Climatic conditions
No corrosive gases
Operating altitude
Max. 2000 m above sea level (80 kPa)
5-150 Hz/1g (EN 60068-2-6)
Vibration resistance
10-500 Hz/3gRMS (IEC 60068-2-64)
Shock resistance
Continuous shock
10g, 16ms (IEC 60068-2-27)
Single shock
30g, 11ms (IEC 60068-2-27)
Electromagnetic
Class A (EN 61000-6-2, EN 61000-6-4)
compatibility
Number of EFI
0
2
interfaces
CPU1: 0
Number of Flexi Line
0
interfaces
CPU3: 2
Data interface
Backplane bus (FLEXBUS+)
CPU1: RS-232
Configuration interface
RS-232
CPU3: RS-232,
USB2.0 (mini b)
Single-core or finely stranded:
1 × 0.14 ... 2.5 mm
2
(26 to 13 AWG) or 2 ×
0.14 ... 0.75mm
2
(26 to 18 AWG)
Finely stranded with wire end ferrules:
1 × 0.25 ... 2.5mm
2
(23 to 13 AWG)or 2 ×
Cross-section of
0.25 ... 0.5mm
2
(23 to 20 AWG)
connecting wires
Monobrin ou fine torsade:
Taille des fils de
1 × 0,14 ... 2,5mm
2
(26 à 13 AWG) ou 2 ×
raccordement
2
0,14 ... 0,75mm
(26 à 18 AWG)
Fine torsade avec manchon d'extrémité EN
46228:
1 × 0,25 ... 2,5mm
2
(23 à 13 AWG) ou 2 ×
2
0,25 ... 0,5mm
(23 à 20 AWG)
EFI or Flexi Line
Dual level spring
-
connection method
clamp terminals
Single-core or finely
stranded:
0.2 ... 1.5 mm
15 AWG)
Cross-section of EFI
-
connecting wires
Finely stranded with
wire end ferrule:
0.25 ... 1.5mm
15 AWG)
Dimensions
22.5 × 96.5 ×
22.5 × 101.7 ×
(W × H × D)
120.8mm
120.8mm
Weight
111g (+/- 5%)
119g (+/- 5%)
Power supply unit (A1, A2) via memory plug WS0-MPL0 or
WS0-MPL1
WS0-CPU0
Supply voltage
24VDC (16.8 ... 30VDC)
Supply voltage
24VDC
UL/CSA applications
PELV or SELV
The current of the power supply unit that
Type of supply
supplies the CPU module has to be limited to a
voltage
maximum of 4A – either by the power supply
unit itself or by a fuse
Overvoltage categoly
II (IEC61131-2)
Power consumption
Max. 2.5W
-9
Switch-on time
Max. 18s
2
(24 to
2
(23 to
WS0-CPU1/3