12. Technical specifications

Voltage range
Insulation voltage
Working ambient conditions
Max altitude
Installation
Connection
Protection
Execution
Color
Ventilation
Noise
Power factor setting
Starting current setting (C/k)
Operation
Losses at 400V 50Hz
Capacitors – QCap type
Reactors (APCQ-R only)
Standards
Short circuit capability
STATUS
Approved
400 / 415 / 600 / 690 V- 50Hz. For other voltages, please consult us.
380 / 480 / 600 / 690 V - 60 Hz For other voltages, please consult us
690V
-5°C (23°F)/+40°C (104°F) according to EN 61921
Humidity: 95% max, not condensing
2000m (for higher altitudes, please consult us)
APCQ-L: wall mounted, bottom cable entry
Clearance lateral: not necessary - top and bottom: 200 mm
APCQ-M and APCQ-R cubicles: free floor standing, bottom cable entry (top ca-
ble entry optional)
Clearance lateral & back: 50 mm (but no clearance required between two
APCQ cubicles)
Three-phase, balanced network.
IP23 (closed door) - optional IP54
Protected against direct and accidental contact (open door)
Indoor
RAL 7035 – Light grey
Forced air cooling
APCQ-L: About 55 dBA (1m)
APCQ-M/R: About 70 dBA (1m)
From 0.7 inductive to 0.7 capacitive
From 0.01A to 3A for the RVC controller
From 0.01A to 5A for the RVT controller (optional)
During operation, RVC (RVT) controller displays:
the number of active outputs
the inductive or capacitive power factor
the alarm conditions: target cos ϕ, over/undervoltage, THDV, overtemperature
the demand for switching on/off a capacitor step
Without reactors: less than 1.5 W/kvar
With reactors: typical 5.5 W/kvar (7 W/kvar maximum in worst case)
Dry type self-healing according to IEC 60831-1&2
Dielectric: 2.15 Un between terminals during 10 sec at rated frequency
Acceptable overvoltage: +10% max. (maximum 8h/day) as per IEC 60831-1
Acceptable overcurrent: +30% permanently
Temperature range: -25°C (-13°F) / class D according to IEC 60831-1&2
Dry type resin embedded according to IEC 289, IEC 76
Maximum harmonic pollution: 8% THDV with specific spectrum. Others under
request
EN 61921
IEC 60831-1&2 (capacitors)
CE marked
50 kA (Icw 1 sec as per IEC 61921)
SECURITY LEVEL
Public
DOCUMENT ID
9AKK107680A4136
AP CQ CAPA CITO R BA NKS
REV.
LANG.
PAGE
E
en
45/47
© 2022 Hitachi Energy. All rights reserved.