Section 19 Technical Support Appendix A - NWGLDE Certifications Appendix B - Console Dimensions Appendix C - Descriptive System Document - LX Plus Appendix D - LX Plus Field Wiring Diagram M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
This connection must have a cross-sectional area of at least 4 mm2 for the added earth connection. WARNING: Substitution of components can decrease intrinsic safety. ADVESTISEMENT: La substitution des composants peut compromettre la sécurité intrinsèque M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 8
READ CAREFULLY: The control drawing shown in ILL. 14 shall be provided with all devices. IMPORTANT: If a replacement power supply cable is necessary, use an applicable, approved ELBZ/7 type power cord. Do not use another type of power cable. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
The table that follows lists reference data of the manufacturer: Data Description Name START ITALIANA S.r.l. Via Natta 6 Address 20823 Lentate Sul Seveso, (MB) Italy Telephone +39 0362 1581465 +39 0362 1581464 Website www.startitaliana.com e-Mail support@startitaliana.it M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 10
INFORMATION: The units of measurement contained in this manual refer to a specified selection by the user. Refer to the M2051 MagLink LX 4/LX Plus Configuration Manual for more information on how to set units of measure. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
DANGER: The console can contain electrical power after it has been shut down. To prevent electrical shock do not open the console to do service for a minimum of two (2) minutes. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 12
This will prevent high voltages sent to the Intrinsically Safe wiring side if there is an electrical fault in the power side. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Label attached under the cable gland related to safety circuit (only if the color of the cable gland is different than blue). Label attached to the ISB-1W, internally. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Instruction against replacing detachable mains supply cords by inadequately 5.4.5 rated cords 5.4.5 The specific replaceable battery type shall be stated M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 15
Aspects resulting from integration into systems or effects resulting from spe- 5.4.6 cial ambient or application conditions shall be described in the doc- umentation M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Install the console in a place that is protected from moisture, direct sun, and water splashes. The console should be installed indoors in a climate-controlled room. CAUTION: The console must be installed in a safe area. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
The power cord must be easy to identify and must have easy access so it can be used to remove power. WARNING: There is high voltage within the console. IMPORTANT: The electrical connection procedure must be done by approved personnel only! 7.4 Installation Procedure M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 19
2. Lift the cover carefully and disconnect the ribbon cable from the rear panel of the console as shown in the illustration above. Put the cover and screws in a temporary safe location where they can be found later and where the components cannot be damaged. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 20
Tap the holes for an applicable screw size or put screw anchors in the hole. NOTE: It is recommended to use size 6 Fischer wall anchors. f. Attach the unit to the wall with the applicable screws. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
The front panel contains the main processing board with the touch screen display and the communication ports. 1. Ribbon cable that connects the back panel with the front panel. 2. Power-IN Yellow (+12V): Terminal 1 Black (-0V): Terminal 2 Not used: Terminal 3 M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Battery With Panasonic Part No. ML621 ONLY. Use of another battery may present a risk of fire or explosion. To avoid possible explosion or fire, do not replace the lithium battery with a type that is not compatible. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
DMP 1-wire probes Smart sensors 8.6 Device Connections to the ISB-1W Internal I.S. Barrier The ISB-1W 12V I.S (Intrinsically Safe) barrier has four channels where probes and sensor can connect. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 24
The maximum number of devices that can connect to the ISB-1W barrier is 12 probes or 48 smart sensors. A range of different device connections can be made. Refer to the illustration below for possible combinations. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
4. DL 5 (yellow): This LED will flash when communication between the auxiliary board and the console mainboard is occurs. When there is no communication for more than 30 secs, the LED will stay on. During a software update the LED will go off. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 26
If a problem occurs when information is saved, the LED will stay on. 6. DL 1 (green) (power): This LED will come on when power is applied to the the auxiliary board. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
"Probe Placement" on the next page "Product Offset Calculation" on page 29 "Riser, Manhole and Junction Box Installation" on page 30 "Conduit Seal Fittings for Cables" on page 33 "Probe Installation in Underground Storage Tanks" on page 36 M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
If the distance is less than this interval, the force of the product that the pump pulls from the tank can cause incorrect indications of the water and product floats. Probe Placement M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
If the probe is located closer to the higher end of the tank, the product offset is positive. For the example above: 1.8”. If the probe is located closer to the lower end of the tank, the product offset is negative; for the example above: -1.8”. Product Offset M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
[Accepts .170" - .470" diameter wire]). The illustration below shows the cap and adapter dimensions and thread specifications for reference. You can keep the cap off of the assembly until after the probe has been put in the tank and riser. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
See the Conduit Seal Fittings for Cables section that follows for more information. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
IMPORTANT: Make sure that the open ends of the prepared cable inside the fitting are completely sealed. This will prevent the flow of explosive fumes through the Cable jacket. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 34
The warranty is voided if incorrect cables, wiring and/or conduit are installed. The ground wire must be correctly installed for the noise-filtering circuitry to operate correctly. Thus, the conduit must not be used for operation of the ground. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
The product float for LPG is not approved for installations where it can be pressurized at or more than 300PSI. Pressures higher than 300PSI will damage the device and it will not be easy to get accurate measurements. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
NOTE: *This is the maximum length of wire to be used to connect all probes on one channel. This length includes the wire from the I.S. barrier to each probe in the string. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 39
NOTE: **ONLY 924B Probes made after September 1, 2007, (version 7.xx firmware) can be installed in a multi-drop installation. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Water level in 0.01 mm Medium temperature detected through digital temperature sensor placed along the probe shaft (max 5) Density range (option): 600-900 Kg/m3 Density Accuracy (option): 3 Kg/m3 Measurement accuracy: < 0.2 mm. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
OIML-R85 11.2 DMP Probe Installation The Dover Magnetostrictive Probe (DMP) is installed almost the same as a 924B Probe. IMPORTANT: To prevent damage to the probe, be careful when you remove the probe from its packaging and when you install it in a tank. Do not let probe components hit the sides of manholes or tank openings.
Page 42
FMS Floats. Make sure the arrow points toward the probe head for ProGauge floats. 3. Attach the End Cap to the end of the probe shaft. Turn it clockwise to tighten. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 43
DMP Probe with FMS Floats M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 44
Carefully lower the probe down into the tank. To prevent damage to the probe, do not let the probe fall and hit the bottom of the tank wall. 5. Connect the 7/8" probe cable connector to the probe. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 45
NOTE: The DMP cable is 1.5 M (3.28 ft.) by default but can be ordered with a different specified length. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
This will keep the probe in the center of the riser and in a vertical position through the bottom of the tank. The Probe Spacer kit contains: One (1) stainless steel, flexible spacer. Two (2) M3x8 screws Two (2) M3 nuts M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 47
This will cause the outer diameter of the vertical strips to move in or out until you find the correct fit inside the riser. When the correct fit has been found, tighten the screws completely. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
For new DMP installations it is recommended to use Belden 88770 for field wiring. The top illustration above shows the wiring of the DMP Probe "One-Wire" to typical field wiring in a waterproof juncion box M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 49
North America. The bottom illustration shows the wiring of the DMP "One Wire" in an IP68 rated junction box for EMEA installations. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
11.4.2 DMP wiring to Belden 88760 NOTE: This is for wiring installations that have Belden 88760 installed. New installations should use Belden 88770 (se the section above). M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 51
DMP Probe "One-Wire" to typical field wiring in a waterproof juncion box for installations in North America. The bottom illustration shows the wiring of the DMP "One Wire" in an IP68 rated junction box for EMEA installations. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
3 kg/m 15.2 cm (6 inches) from the bottom of the probe Suggested Location: NOTE: Use two (2) set screws at the top of the float to hold it in position M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 53
4. Put the water float, nylon probe foot and end clip back on the probe shaft. 5. Put the probe back in the tank. 6. Turn on the power to the module. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
(2 inches) to this distance to include the dead zone at the end of the probe. The result is the value of the minimum Low-Low product threshold. Calculate Low-Low Threshold M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
8. For the configuration and calibration, you will need the A and B parameters printed on the body of the float. These parameters are also written on the label inside the float packaging. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
(hydrometer); the B parameter will change according to the alignment. The calibration process will be shown in the configuration section of your console. The density kit can lose its calibration because of the weight of possible contamination. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Specifications 30-0230-S: STP Sumps and Fuel Dispenser Pans Primary Use: 30-0231-S: Interstitial Area 30-0230-S: Steel Tank Interstitial Alternate Use: 30-0231-S: Sumps and Fuel Dispenser Pans M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 62
Systems 12V VSmart Module. This will make sure that operation conditions are safe. Smart Sensors CANNOT be used with SS1, 2 or 3, iTouch or EECO consoles. CAUTION: ALWAYS obey Local and National Electrical Codes applicable to the installation location. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 63
Install explosion-resistant sealing fittings at both ends of the conduit. Refer to the Probe-Cable Seal- offs section of the console's Installation Guide for instructions. Connections Sensor Wire Color 12V Smart Sensor Interface Channel Power Black (hydrocarbon sensor) Signal Shield (or 3rd conductor) Ground M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 65
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection. Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and the console. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 66
Look to see if the float is in the correct position (refer to the applicable instruction above). A sensor or wiring fault will cause a system alarm. Do a continuity test in the wiring and junction boxes. Make sure there is continuity with no short circuits. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Diameter: 7.4 cm (2.90 inches), 9.5 cm (3.70 inches) Belden #88760 or Alpha #55371 Cable Requirements: 3.6m (12 feet) of gas & oil resistant cable to the inline ISIM + 1.3m (4 feet) ISIM tail. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 68
To monitor a normally wet well, use a meter to set the float so that the sensor is in a closed condition WITH a liquid level (the float will be in the upper position). This sensor uses ONE Controller Interface I.S. Module position M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 69
Installation Guide for instructions. Connections Sensor Wire Color 12V Smart Sensor Interface Channel Power Black (hydrocarbon sensor) Signal Shield (or 3rd conductor) Ground Typical Installation Drawing M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 70
Look to see if the float is in the correct position (refer to the applicable instruction above). A sensor or wiring fault will cause a system alarm. Do a continuity test in the wiring and junction boxes. Make sure there is continuity with no short circuits. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
If there is a break in the cable it will cause an alarm condition in the system. Specifications D-10: Fuel Dispenser Pan/Sump Primary Use(s): D-20: STP Sumps D-10: STP Sumps Alternate Uses: D-20: Fuel Dispenser Pan/Sump M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 72
Hazardous Areas section of your console's Installation Guide before you install or do the servicing of this sensor. CAUTION: ALWAYS obey Local and National Electrical Codes applicable to the installation location. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 73
Install explosion-resistant sealing fittings at both ends of the conduit. Refer to the Probe-Cable Seal- offs section of the console's Installation Guide for instructions. Connections Sensor Wire Color 12V Smart Sensor Interface Channel Power Black (hydrocarbon sensor) Signal Shield (or 3rd conductor) Ground M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 74
Put the float in the HIGH position. This will cause an alarm condition in the controller. Put the float back in the LOW position. Make sure that the controller is not in an alarm condition. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 75
Look to see if the float is in the correct position (refer to the applicable instruction above). A sensor or wiring fault will cause a system alarm. Do a continuity test in the wiring and junction boxes. Make sure there is continuity with no short circuits. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Two (2) float switches are used in the body of the sensor to sense low and high liquid levels. If there is a break in the cable it will cause an alarm condition in the system. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 77
More than 30,000 ohms Belden #88760 or Alpha #55371 Cable: 3.6 m (12 feet) of gas & oil resistant cable to the inline ISIM + 1.3 m (4 feet) ISIM tail M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 78
Systems part # 12-1030) from the field wiring to the controller are in conduit that is dedicated to intrinsically safe wiring. Use wire-nuts and epoxy-resin seal-packs for North American field connections (refer to M00-390008 Waterproof Electrical Connections for information). M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 79
Installation Guide for instructions. Connections Sensor Wire Color 12V Smart Sensor Interface Channel Power Black (hydrocarbon sensor) Signal Shield (or 3rd conductor) Ground Typical Installation Drawing M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 80
Do not use fuel (gasoline, diesel etc.) to test or clean the sensor! Once the carbon/polymer material has touched liquid hydrocarbon, it is possible that the sensor will not return to its initial electrical resistance. This can have an unwanted effect on its M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 81
NOTE: If the sensor does not return to near its original resistance after you do a functional test or contamination has been removed, it is recommended to replace the sensor. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Since this sensor is not made to sense hydrocarbons it does not use a carbon/polymer strip. No Carbon/Polymer Strip M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 83
1 to 2 (upper float in alarm - top and bottom floats in the up position) Maximum points per channel = 12 points Multi-Drop Restriction 924B and DMP Probes = 4 points ISIM Smart Sensors = 1 point M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 84
Seal the electrical connections with the epoxy seal packs (refer to M00-390008 Waterproof Electrical Connections for instructions). Install explosion-resistant sealing fittings at both ends of the conduit. Refer to the Probe-Cable Seal- offs section of the console's Installation Guide for instructions. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 85
Connections Sensor Wire Color 12V Smart Sensor Interface Channel Power Black (hydrocarbon sensor) Signal Shield (or 3rd conductor) Ground M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 86
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection. Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and the console. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 87
Look to see if the float is in the correct position (refer to the applicable instruction above). A sensor or wiring fault will cause a system alarm. Do a continuity test in the wiring and junction boxes. Make sure there is continuity with no short circuits. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
NOTE: *This is the maximum length of wire to be used to connect all sensors on one channel. This length includes the wire from the Barrier to each sensor board in the string. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 89
Install explosion-resistant sealing fittings at both ends of the conduit. Refer to the Probe-Cable Seal- offs section of the console's Installation Guide for instructions. Connections Sensor Wire Color 12V Smart Sensor Interface Channel Power Black Signal Shield Ground M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 90
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection. Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and the console. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 91
Disconnect the Water Sensor from the I.S. terminal strip in the controller. The test is satisfactory if NO alarm condition occurs. Connect the sensor back to the I.S. terminal strip. Short across the power and signal terminals. This test is satisfactory if an alarm condition occurs. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 92
NOTE: If the sensor does not return to near its original resistance after you do a functional test or contamination has been removed, it is recommended to replace the sensor. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
ISIM Smart Sensors = 1 point Devices can be mixed in any combination to hold a maximum of 12 points on one channel Connections: Red = Power, Black = Signal, Shield = Ground M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 94
Seal the electrical connections with the epoxy seal packs (refer to M00-390008 Waterproof Electrical Connections for instructions). Install explosion-resistant sealing fittings at both ends of the conduit. Refer to the Probe-Cable Seal- offs section of the console's Installation Guide for instructions. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 95
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection. Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and the console. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 96
A sensor or wiring fault will cause a system alarm. Do a continuity test in the wiring and junction boxes. Make sure there is continuity with no short circuits. Functional Test - Water Sensor of the Device M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 97
NOTE: If the sensor does not return to near its original resistance after you do a functional test or contamination has been removed, it is recommended to replace the sensor. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Interstitial areas of a double-walled tank Detects: Hydrocarbon vapor Operating Temperature: -40°C to +70°C (-40°F to 158°F) Dimensions: Length: 8.9 cm (3.5”), Diameter: 2.3 cm (0.9”) Nominal resistance (uncontaminated) Less than 5,000 ohms M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 99
Systems part # 12-1030) from the field wiring to the controller are in conduit that is dedicated to intrinsically safe wiring. Use wire-nuts and epoxy-resin seal-packs for field connections (refer to M00- 390008 Waterproof Electrical Connections for information). M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 100
Install explosion-resistant sealing fittings at both ends of the conduit. Refer to the Probe-Cable Seal- offs section of the console's Installation Guide for instructions. Connections Sensor Wire Color 12V Smart Sensor Interface Channel Power Black (hydrocarbon sensor) Signal Shield (or 3rd conductor) Ground M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 101
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection. Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and the console. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 102
Remove the sensor and let it dry in the air for one (1) hour. Reconnect the sensor. NOTE: If the sensor does not return to sufficient resistance, replace the sensor if necessary. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
+ 1.3 m (4 feet) ISIM tail Maximum Wiring Length*: 305 m (1,000 ft.) field wiring Alarm Threshold Configuration: Fully Automatic 0.02 to 0.03 and 0.23 to 0.25 (normal), Diagnostic Reading on Sensor Setup: M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 104
Systems part # 12-1030) from the field wiring to the controller are in conduit that is dedicated to intrinsically safe wiring. Use wire-nuts and epoxy-resin seal-packs for field connections (refer to M00- 390008 Waterproof Electrical Connections for information). M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 105
Install explosion-resistant sealing fittings at both ends of the conduit. Refer to the Probe-Cable Seal- offs section of the console's Installation Guide for instructions. Connections Sensor Wire Color 12V Smart Sensor Interface Channel Power Black (hydrocarbon sensor) Signal Shield (or 3rd conductor) Ground M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 106
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection. Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and the console. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 107
A sensor or wiring fault will cause a system alarm. Do a continuity test in the wiring and junction boxes. Make sure there is continuity with no short circuits. TIP: This sensor can be cleaned with a dry cloth and put back into service again immediately. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Install the three (3) cover screws. Connect the power cable. Energize the main electrical panel. Put the power switch of the console in the ON ("I") position. The console will now start up. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
IMPORTANT: It is recommended to not have more than 15 meters for serial connections between the console and the management system through RS232. 17.2.1 GILBARCO Fuel Management System The illustration and table below show the connection for the Gilbarco fuel management system: M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Do not use compressed air or liquid detergents to clean the touchscreen or the console. Clean the touchscreen and the outside of the console with a monitor/TV cleaning cloth. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Refer to the "Utility" section of the M2051 LX 4 Configuration manual for for information on log files and the database backup in the console. M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Appendix D - LX Plus Field Wiring Diagram M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Page 123
# smart sensors on barrier from 24 to 48, add DMP Probe specs, add DMP Density Float, add Wiring Diagram. NOTE: It is possible that older software versions might not support all features M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions...
Need help?
Do you have a question about the ProGauge MagLink LX Plus and is the answer not in the manual?
Questions and answers