Technical Data - Viking MICROFAST VK354 Technical Data Manual

Quick response conventional sprinkler

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast
®
distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Sprinkler Temperature
Classification
Ordinary
Ordinary
Intermediate
Intermediate
High
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings
The sprinkler temperature rating is stamped on the deflector.
1
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
2
Refer to specific installation standards.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e. These tests
3
cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible
with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note
that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
Form No. F_033214
18.11.05
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Quick Response Conventional Sprinkler VK354 is available through a network of domestic and international
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Nominal
Temperature Rating
135 °F (57 °C)
155 °F (68 °C)
175 °F (79 °C)
200 °F (93 °C)
286 °F (141 °C)
: White Polyester and Black Polyester. ENT in all temperature ratings except 135 °F (57 °C)
3
Protective Sprinkler Cap
Wrench Flat
Standard Sprinkler Wrench 21475M/B
Rev 18.3.P65

TECHNICAL DATA

1
Footnotes
Figure 1:
MICROFAST
RESPONSE CONVENTIONAL
SPRINKLER VK354 (K8.0)
Maximum Ambient
Ceiling Temperature
2
100 °F (38 °C)
100 °F (38 °C)
150 °F (65 °C)
150 °F (65 °C)
225 °F (107 °C)
Page 2 of 3
QUICK
®
Bulb Color
Orange
Red
Yellow
Green
Blue