SALES - Product Information, Systems Application Questions, and placing orders for standard products and special systems. Please mailto: sales@dfe.com call (603) 332-6150 and ask for Sales or email to us at sales@dfe.com Telephone: (603) 332-6150 Fax: (603) 332-3758 E-mail: info@dfe.com Internet: www.dfe.com...
Page 3
Make sure you read and understand all instructions and safety precautions listed in this manual before installing or operating your TA1 True Tension Amplifier. If you have any questions concerning the operation of your device or the information in this manual, please contact us. Email: techsupport@dfe.com Telephone: (603) 332-6150 • Observe all warning labels.
The amplifier boosts the millivolt- level tension-signal input from a DFE tension transducer (or transducer pair) to output a proportional 0-10 VDC (isolated) and 4-20 mA signal to a PLC, drive or display meter.
INSTALLATION 2.1. Dimensions FIGURE 1 - Dimensions 2.2 Mounting the Unit The unit is DIN rail mountable, compatible with DIN35mm rail. Snap on to mount. To remove from the DIN rail, use a screwdriver and release the clamp as shown below. FIGURE 2 - Removing from DIN Rail...
2.2 Mounting the Unit continued... The unit can also be screw mounted. By adjusting the top and bottom clips to the outer positions. FIGURE 3 - Convert to Screw Mount 2.3 Standard Electrical Connections 1. Power Input Power should be sourced to the TA1 on Pins 1 (GND) and 2 (+24 VDC) FIGURE 4 - Power Input Connections 2.
2.3 Standard Electrical Connections continued..3. Transducers / Load Cells FIGURE 6 - Transducer Electrical Connections (See Appendix A for full Electrical Connections) Below is label on left side of unit:...
2.4 Optional Electrical Connections 1. CAL A/B (Dual Calibration) Dual Calibration allows two calibration settings. To operate the TA1 amplifier in the Calibration A configuration the connection to PIN 6 must be left open. To operate the TA1 in the Calibration B configuration the 24V must be applied to PIN 6.
OPERATION 3.1 Hardware Identification FIGURE 9 - Location of Zero, Cal Buttons and Status LED 3.2 Calibration A calibration process must be performed before your amplifier is ready to indicate tension. Select an appropriate calibration weight. The weight determines the value of web tension that will produce full output of the TA1.
3.2 Calibration continued..FIGURE 10 - Web Path To calibrate at 10%: Push and Hold the Cal Button (About 1 Second) until confirmation blinks, then release the button. The output will read 10% of full scale after calibration. To calibrate at 25%: Push and Hold Cal Button (About 10 Seconds) until you see two sets of confirmation blinks.
• 4 Blinks = Excitation Failure or Wiring Error Action Required: Check for shorts in the transducer / load cell wiring. If the transducers need trouble shooting – contact tech support for assistance. • 5 Blinks = DAC/ADC Internal Failure Action Required: Contact DFE for replacement.
(SPRs), product manufactured specially to customer specifications, and 3. GOVERNING LAW non-DFE product purchased on customer behalf shall not be returnable This contract shall be governed by and construed according to the laws for any reason. All material returned, for whatever reason, shall be sent of the state of New Hampshire, U.S.A.