INSTRUCTION MANUAL EtherNet/IP™ Tension Amplifier Model TA500-EIP...
Page 2
Manuals. Call (603) 332-6150 and ask for Customer Service or email us at: customerservice@dfe.com SALES Product Information, System Application Questions or Placing Orders, Please e-mail us at: sales@dfe.com or call (603) 332-6150 and ask for Sales. Telephone: (603) 332-6150 Fax: (603) 332-3758 E-mail: info@dfe.com Internet:...
Page 3
Make sure you read and understand all instructions and safety precautions listed in this manual before installing or operating your TA500-EIP Tension Amplifier. If you have any questions con- cerning the operation of your device or the information in this manual, please contact us.
DOCUMENT CONVENTIONS NOTES - Highlight important concepts, decisions you must make, or the implications of those decisions. CAUTIONS - Tell you when equipment may be damaged if the procedure is not followed properly. WARNINGS - Tell you when people may be injured, or equipment may be damaged if the procedure is not followed properly.
Legacy push button calibration is supported to allow fast commissioning. With this method machine builders will find the TA500-EIP very familiar to existing DFE tension amplifiers. Once calibrated, the amplifier will pro- vide a simultaneous tension signal out in the format of 0-10V and 4-20mA. Optionally an EtherNet/IP™ con- nection can be established and the tension data will be available through the EtherNet/IP™...
1.5 STATUS LED Amplifier Status Information is useful for determining the condition of the tension amplifier and its network and module operational state. Three bi-colored LEDs located on the front of the TA500-EIP provided this infor- mation. Amplifier Status LED The Amplifier Status LED is a bi-color red/green LED.
Page 9
Module Status (MS) LED The Module Status LED is a bi-color red/green LED. The state of the LED depends on the state of the network adapter module. MS LED STATE DEFINITION Power off. Steady Green Device in operation. Flashing Green Standby device, not configured, no IP ad- dress assigned.
2 INSTALLATION & MOUNTING The unit is DIN rail mountable, compatible with 35mm DIN rails. To install snap on to DIN rail. To remove from the DIN rail, use a screwdriver and release the clamp at bottom of the unit as shown below. TA500 Devices shall be vertically mounted.
Pin 15: - EXCITATION o Pin 16: Shield (Tied to Functional Earth Ground Connection) TA500-EIP meets the European Union's Low Voltage Directive and EMC Directive only when installation is done correctly. To meet the EMC Directive, a proper transducer installation, including...
DLR provides a means to detect, manage, and recover from single faults in a ring-based network. In De- vice Level Ring applications, the TA500-EIP unit functions as a Beacon-Based Ring Node. In these appli- cations, both ports are used when wiring the ring, daisy chaining from one unit in the ring to the next.
The weight determines the value of web tension that will be produced at full output of the TA500-EIP. The TA500-EIP allows calibration to be performed with 10% or 25% of the full range desired.
Checking Active Connections. Confirm that the TA500-EIP has a valid link to your network and an assigned or specified IP. The default IP address programmed at the factory is 192.168.1.230. If you are unsure what the IP address is see the section Finding the IP address.
Page 15
3. Find the “CalUnits” parameter and select the desired unit for calibration and press “Set”. 4. Find the “CalRange” parameter and select the desired range for calibration and press “Set”. Zero: 1. Ensure the transducer load cells are installed in the intended configuration and that nothing, including any rope used to hang calibrations weights, is loading the load cells.
Page 16
Calibrate: During the calibration, the transducer(s) should be loaded. Fasten one end of the rope in the machine and thread the other end around the transducer roll in the same path the web will take. Be sure the rope does not pass around any driven rolls, drag bars, or anything else that can affect tension.
While the calibration weight is still hanging, the tension percent reading shall correspond to the calibration per- centage. In the example above, the TensionPercent parameter is read as 25.0 as the register holds the tension value with 1 decimal place format. The CalTension parameter holds the calibrated tension value with 2 decimal places format.
All Dover Flexo Electronics' EDS files are located on our website at the following address: https://dfe.com/products/tension-amplifiers/ta500-eip-tension-amplifier-2/ 5.2 INSTALLING THE EDS FILE With Studio 5000 running, in the menu bar select Tools -> EDS Hardware Installation Tool. This will open the...
Page 20
1. Click next to continue. 2. Select the “Register an EDS file(s)” and click next. 3. Select the “Register a single file” and click next.
4. The Wizard will show that the import is scanned for errors and is error free. Click next. 5. Click Next unless you want to change the default icon. Click Ok to add the device. EDS installation is complete. 5.3 SYSTEM CONFIGURATION WITH STUDIO5000 This section covers the installation and use of the EDS file for systems that are programmed with Rockwell Automation Studio 5000 version 20 and above.
Page 22
2. Search for “TA500” in the applicable Filters. 3. Select “Tension Amplifier TA500-EIP” in the resulting list. 4. Click on the [Create] button to create the module. 5. Click on [Close] if necessary, to close the Select Module Type screen 6.
5.4 TENSION DATA AND STATUS After the module is added input Tags carry the calibrated tension value if the unit is calibrated and other status information of the device. If calibration of the unit is required see the section Calibration. All tag data is Signed 32–bit integer value.
Page 24
ADC_VALUE – Raw value of input signal from load cells. Useful for troubleshooting or by advanced users. TENSION_P - Tension value in percent of total calibrated range. Format: 1 decimal. If the calibration was performed using the zero and calibration button on the TA500 then the calibration performed can be considered unitless and range-less unless the value in the CalRange Reg- ister and the CalUnits register at calibration was valid.
Page 25
CAL_RANGE – The calibration range can be stored with the calibration. This data in this tag must be valid when sending the calibration command for the unit to be stored. Value Definition 1000 1250 1500 2000 2500 3000 4000 5000 COMMAND –...
Status Bit section for the bit location. 6.1 FINDING THE IP ADDRESS If the IP address of the TA500-EIP is unknown, there are a few methods which can be used to find its current IP address or re-establish a default IP.
The TA500-EIP uses the HMS NP40 chipset for its network processor architecture. HMS provides a tool to lo- cate devices on the network called the HMS IPconfig Tool. It is free to download from HMS Anybus webpages https://www.anybus.com/support Using this tool makes it easy to view device types and verify network IP configurations.
Using the Web Interface Navigate to Status The TA500-EIP also indicates active connections using the status LEDs at the front of the device. When an established connection is active the Network status LED will be solid green. For more information see the sec-...
15%. Special Product Requests (SPRs), product manufac- proceedings pursuant to this contract shall take place under the jurisdiction tured specially to customer specifications, and non-DFE product purchased of the courts of the State of New Hampshire in the judicial district of Straf- on customer behalf shall not be returnable for any reason.