Always switch off power supply before starting any work on the unit.
Installation
Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed. Before drilling the
enclosure, ensure the fixing elements and couplings will not interfere with the equipment inside the enclosure itself. When
all mounting preparations are complete, the actual mounting operation can commence. Only use the enclosed material to
mount the unit on the cabinet.
Proceed as follows to mount the unit on the enclosure:
• Set the unit up on the enclosure.
• Ensure that the electrical connection is above the internal fan.
• Unit without duct: screw the M6 locknuts & washers into the M6 set screws in the unit.
• Unit with duct: screw the M6 screws & washers into the M6 threaded rivets in the unit.
The resistance of the earth connection between cabinet and cooling unit must be <0.1 Ω.

8. Mounting

7