Safe Fleet FoamPRO AccuMax 3020 Installation And Operation Manual

Single-point injection systems

Advertisement

Quick Links

Single-Point Injection Systems
Models 3020/3040/3060/3090/3150/3300
All quality FoamPro products are ruggedly designed, accurately machined, carefully assembled, thoroughly inspected
and tested. In order to maintain the high quality of your unit, and to keep it in a ready condition, it is important to follow
the instructions on care and operation. Proper use and good preventive maintenance will lengthen the life of your unit.
ALWAYS INCLUDE THE UNIT SERIAL NUMBER IN CORRESPONDENCE.
FoamPro • 26 Southern Blvd. • Nesconset, NY 11767 USA • 800-533-9511 • FAX 816-892-3178
AccuMax
INSTALLATION AND
OPERATION MANUAL
Unit
Serial
Number
Form 903
Rev. 8/19
1

Advertisement

Table of Contents
loading

Summary of Contents for Safe Fleet FoamPRO AccuMax 3020

  • Page 1 Form 903 Rev. 8/19 AccuMax Single-Point Injection Systems Models 3020/3040/3060/3090/3150/3300 INSTALLATION AND OPERATION MANUAL Unit Serial Number All quality FoamPro products are ruggedly designed, accurately machined, carefully assembled, thoroughly inspected and tested. In order to maintain the high quality of your unit, and to keep it in a ready condition, it is important to follow the instructions on care and operation.
  • Page 2: Table Of Contents

    Installation and Operation Manual Installation and Operation Manual TABLE OF CONTENTS SECTION PAGE SAFETY ........................... 3 A QUICK LOOK AT HOW THE SYSTEM WORKS ............5 SYSTEM COMPONENT DESCRIPTION ................. 7 INSTALLER SUPPLIED PARTS ..................9 INSTALLATION PLANNING ................... 12 FOAM PUMP &...
  • Page 3: Safety

    AccuMax SP Installation and Operation Manual Installation and Operation Manual Before attempting to install a FoamPro AccuMax System, read all Safety of the following safety precautions and follow carefully. The following special notices are used to notify and advise • Any electrical system has the potential to cause the user of this product about procedures that may be sparks during service.
  • Page 4 Installation and Operation Manual Installation and Operation Manual WARNING: Always disconnect the ground straps, CAUTION: The foam tank low-level sensor must be electrical wires and control cables from the Digital utilized to protect the foam pump from dry running. Display Control Module and all other FoamPro Failure to do so will void warranty.
  • Page 5: A Quick Look At How The System Works

    AccuMax SP Installation and Operation Manual Installation and Operation Manual A Quick Look at How the System Works The FoamPro AccuMax Single-Point system is Foam concentrate is injected directly into the water an electronically-controlled, hydraulically-driven, stream on the discharge side of the water pump. It is foam concentrate proportioning system designed to then fed as foam solution into a standard fog nozzle, provide the wide range of foam concentrate injection...
  • Page 6 Installation and Operation Manual Installation and Operation Manual Figure 2-1 FoamPro 3000 System Layout...
  • Page 7: System Component Description

    AccuMax SP Installation and Operation Manual Installation and Operation Manual System Component Description The following components are packaged with the 11. FoamPro Paddlewheel Flowmeter (The flowmeter standard FoamPro AccuMax SP system: is a required component. The size is specified and ordered under a separate part number when the 1.
  • Page 8 Installation and Operation Manual Installation and Operation Manual System Accessories Available System Specification Placards System Part Number 3020 6032-0028 3040 6032-0030 3060 6032-0032 3090 6032-0070 3150 6032-0048 3300 6032-0073 Main Waterway Check Valve with Drain Port Size/ Thread All Stainless Steel 1-1/2"...
  • Page 9: Installer Supplied Parts

    AccuMax SP Installation and Operation Manual Installation and Operation Manual Installer Supplied Parts FoamPro AccuMax SP systems are provided with major components and accessories required for Control of the PTO may be provided by a manual shift installation. Due to differences in chassis and apparatus lever, shift cable, or solenoid.
  • Page 10 Installation and Operation Manual Installation and Operation Manual Oil Cooler Model Min. Hose ID An oil cooler capable of maintaining the temperature 3020/3040 1-1/2" 3060 2" of the hydraulic oil at 140° to 180°F (60° to 82°C) is 3090 2-1/2" required.
  • Page 11 AccuMax SP Installation and Operation Manual Installation and Operation Manual Check Valves Electrical Requirements It is required by NFPA to install a check valve in the foam Electrical power and wiring must be supplied from the concentrate injection line to prevent foam concentrate main apparatus electrical system to the AccuMax SP flow from the foam tank to the injection point (at the main system.
  • Page 12: Installation Planning

    Installation and Operation Manual Installation and Operation Manual Installation Planning Because of the potential differences in apparatus Determine a location on the operator panel of the plumbing and foam system configuration, it is not apparatus for the Digital Display Control Module. practical to depict exactly how each FoamPro unit can Consideration must be given for routing the control best be installed onto a particular apparatus.
  • Page 13: Foam Pump & Hydraulic Control Valve Installation

    AccuMax SP Installation and Operation Manual Installation and Operation Manual Installation and Operation Manual Foam Pump and Hydraulic Control Valve Installation Hydraulic-Driven Foam Pump Assembly Choosing the Proper PTO The AccuMax systems are designed to be used with It is important to turn the hydraulic pump at the proper various gear type foam pumps currently in use in the speed to ensure that the correct hydraulic pressure is industry.
  • Page 14: Hydraulic Plumbing Installation

    Installation and Operation Manual Installation and Operation Manual Hydraulic Plumbing Installation Figure 7-1 provides some recommended guidelines for CAUTION: Use only approved petroleum-based hydraulic fluids as described in Section 4. Never the location of the hydraulic system components. When making hydraulic component connections ensure all mix fluid types.
  • Page 15 AccuMax SP Installation and Operation Manual Installation and Operation Manual Hydraulic Reservoir Hydraulic Oil Cooler The hydraulic reservoir for the system is to conform An oil cooler is required in the hydraulic system to to the description in Section 4 and to all SAE and ensure proper oil temperature for optimum performance DOT standards.
  • Page 16: Water And Foam Plumbing Component Installation

    Installation and Operation Manual Installation and Operation Manual Water and Foam Plumbing Component Installation The following diagram (Figure 8-1) provides options such as dual-tank system, multiple flowmeters, recommended guidelines for the installation of etc., are covered by the individual manuals included the system components that handle water, foam with those systems and consideration must be given to concentrate and foam solution.
  • Page 17 AccuMax SP Installation and Operation Manual Installation and Operation Manual Line Strainer CAUTION: Flexible hose connections are required between the major FoamPro components and the The line strainer(s) provided with the FoamPro AccuMax main water system. Do not hard plumb the system. SP system are sized properly for most applications.
  • Page 18 Installation and Operation Manual Installation and Operation Manual Model Pipe Minimum Straight Run Pipe Size Before After Flowmeter Flowmeter 3020& 3040 3/4" 8-1/4"(210 mm) 4-1/8"(105mm) 3060 1" 8-1/4”(210 mm) 4-1/8"(105mm) 3090 1-1/4" 8-1/4”(210 mm) 4-1/8"(105mm) 3150 1-1/2" 10-1/4”(260 mm) 5-1/4"(133 mm) 3300 2"...
  • Page 19 AccuMax SP Installation and Operation Manual Installation and Operation Manual Flowmeter Injection Port (Optional location on other side of Flowmeter) Injector Above Main Waterway Horizontal Plane DON’T Check Valve Drain Port Minimum length of nipple for Injector Below 2-1/2’’ pipe is 12-1/2’’ (318 mm). Horizontal Plane Refer to Table on Page 20 for recommended nipple lengths for...
  • Page 20 Installation and Operation Manual Installation and Operation Manual Drain Lines On apparatus with multiple drain lines, the drains Switch to disconnect Level Sensor when in from the foam solution discharge line should not Outboard be piped into a multi-drain system before the check Foam valves.
  • Page 21: Electrical Equipment Installation

    AccuMax SP Installation and Operation Manual Installation and Operation Manual Electrical Equipment Installation Electrical Connections Warning: The electric motor-driven foam pump contains a capacitor on the input power. Connect Follow the system electrical diagram (Figure 9-1) for leads with battery off or disconnected. Current will proper hookup of each of the electrical components.
  • Page 22 Installation and Operation Manual Installation and Operation Manual NOTE: Do not mount radio transmitter or transmitter cables in direct or close contact with the FoamPro units. • Use care when installing molded cables. Count pins or check color codes before connecting. Bent pins caused by improper hookup can prevent proper operation even when cables are reattached properly.
  • Page 23 AccuMax SP Installation and Operation Manual Installation and Operation Manual MultiFlo Flowmeter Interface Modules When the bottom of the tank is not accessible, the foam tank low-level sensor can be hung from a long Refer to the MultiFlo Interface instructions for installations pipe nipple attached to the top of the tank.
  • Page 24 Installation and Operation Manual Installation and Operation Manual A side-mount foam tank low-level sensor is available The system will draw an approximate maximum of 5 to be used if both the top and bottom of the is not Amperes and must be protected with a 10 Amp fuse accessible.
  • Page 25 AccuMax SP Installation and Operation Manual To Other Devices Master Disconnect Switch, PTO Switch, or Manual Switch Pin B (-) Battery Pin A (+) Common Ground Connection Relay, or Solid Common State Contactor Power Connection +12 VDC – 10 Amp Fuse +24 VDC –...
  • Page 26 Installation and Operation Manual Installation and Operation Manual Hydraulic Motor-Driven Foam Pump Driver Box Modular Cable Large Beads Control Cable Wire Ties Large Control DON’T Cable Beads Flowmeter Cable Modular Cable Small Beads Figure 9-8 Extra Cable Storage Digital Display Control Module Flowmeter Figure 9-7 RFI/EMI Bead Installation...
  • Page 27 AccuMax SP Installation and Operation Manual Installation and Operation Manual Manual Override (Optional) The Manual Override option allows the operator to disengage the automatic proportioning system and control the foam pump manually. The manual override will allow the usage of the hydraulically-driven foam pump to deliver foam to the water lines.
  • Page 28 Installation and Operation Manual The following procedure should be used when engaging this operation: 1. Turn off AccuMax Display Controller. 2. Turn the Manual Override switch to the ‘OFF’ position. The AccuMax displays should not be illuminated. 3. Close the 2-way manual foam control valve (not supplied) feeding the discharge line being used until it is about 1/4 of the way open.
  • Page 29: Make Sure Everything Is Working Right

    AccuMax SP Installation and Operation Manual Make Sure Everything Is Working Right Hydraulic Supply (Refer to Sections 4 and 7) • Hydraulic pump is properly mounted to the PTO. • Hydraulic oil lines are properly routed and tight. • Filter(s) are installed and tight. •...
  • Page 30 Installation and Operation Manual System Power Check • Operate the fire truck engine so that hydraulic oil pressure is available. Put the system in “Simulated Turn the main power switches on the Hydraulic Valve Flow Mode” by selecting the FLOW display and Driver and Motor Driver Modules to ON and check the depressing RESET, (both UP and DOWN buttons digital display readout.
  • Page 31 AccuMax SP Installation and Operation Manual Perform Steps 1 through 3 to wet the foam pumps • to speed the priming operation. 1. Remove the pipe plug from the top of the gear pump. 2. Fill the pump with concentrate. 3.
  • Page 32: Calibration And Setup

    Installation and Operation Manual Calibration and Setup System Setup Procedures FoamPro systems permit easy calibration of the foam proportioning unit to assure accurate operation. The Remove for Remove for calibration process will make adjustments to the Setup and Calibration Diagnostic and Setup flowmeter(s) and foam pump display readings.
  • Page 33 AccuMax SP Installation and Operation Manual Flowmeter Calibration injection rate stored in the computer memory as PC x.x. The buttons can be used to set NOTE: It is critical that an accurate flow measuring DOWN the desired concentrate injection rate. Set this rate to device be used to measure water flow to calibrate the foam concentrate injection rate used most frequently the flowmeter(s).
  • Page 34 Installation and Operation Manual System Reset A calibrated flowmeter with a totalizer can also be used in-line to directly measure the foam being pumped and During calibration procedures, it may be necessary to is available by ordering Part No. 3430-0831. return the system to the original factory default settings if errors are made and the system locks up.
  • Page 35: Operation Instructions

    AccuMax SP Installation and Operation Manual Operation Instructions Normal System Operation the ON status lamp will extinguish, indicating that the system is in Standby mode and the foam pump will stop, Once the system has been set up and calibrated, but other system monitoring functions will continue.
  • Page 36 Installation and Operation Manual Foam Percentage (%) If the flow decreases so the required injection rate is less than the lowest rating of the pump, the pump will When the concentrate percentage (%) is selected, run at its minimum rate and LO.FLO will flash on the buttons will respectively increase or down display to let the operator know the system is running...
  • Page 37 AccuMax SP Installation and Operation Manual Normal Operation Summary How to Action Display 1. Turn FoamPro system on. 1. Operate the apparatus engine to develop hydraulic pressure. Turn the FoamPro Main Power circuit breaker switch on. HYPRO will appear on the display momentarily.
  • Page 38 Installation and Operation Manual Normal Operation Summary How to Display Action 6. Read the total amount of foam 6. Press the SELECT button concentrate used. (white upper-right button) until the LED lamp below the TOTAL FOAM label is illuminated. The total amount of foam concentrate used will be displayed.
  • Page 39 AccuMax SP Installation and Operation Manual Simulated Flow Operation Warning: When operating the FoamPro in the Simulated Flow function, an outlet for the foam The Simulated Flow function of the system allows the concentrate injection must be provided. Otherwise, operator to control the foam pump manually. The water dangerous excessive pressure may be built up flow rate and the concentrate injection percentage in the apparatus water piping and or hoses.
  • Page 40 Installation and Operation Manual Simulated Flow Operation Summary How to Display Action 4. Place a suitable container 4. Empty the Foam Tank. under the CAL/FLUSH outlet tube. Place the CAL/INJECT valve in the CAL/FLUSH position. Press the FOAM button. The foam pump will operate and foam concentrate will be discharged from the outlet tube.
  • Page 41 AccuMax SP Installation and Operation Manual Flushing Foam Pumps Priming the Foam Pump When Foam Tank When returning the apparatus to ready condition after Has Run Dry foam operations, the FoamPro foam pumps should be In some instances, the foam tank may run dry while flushed with fresh water.
  • Page 42: Maintenance

    Installation and Operation Manual Maintenance Maintenance Procedures 7. Bi-Annually: Change hydraulic oil filter. 3040 Filter 3800-0100 1. After each use: It is recommended as good 3060 thru 3300 3800-0101 practice to flush the FoamPro AccuMax 3000 system foam pump after each use. The system 8.
  • Page 43: Troubleshooting

    AccuMax SP Installation and Operation Manual Troubleshooting Entering Diagnostic Mode flowmeter. Removing the flowmeter sensor from its tee and spinning the paddlewheel should produce a reading Diagnostic mode is entered by removing the Cover other than zero on the display. Screw and O-ring on the right-hand side of the Digital Display Control Module (See Figure 14-1) using a 3/32’’...
  • Page 44 Installation and Operation Manual Foam Tank Low-Level Sensor Foam Flowmeter Large Beads Control Cable Flowmeter Cable To 12 or 24 VDC Small Beads Digital Display Control Module Flowmeter Figure 14-2 Electrical Wiring Diagram Symptom Probable Cause(s) Corrective Action Pump does not run. ERR.HY Hydraulic pump not properly Check and attach cables display.
  • Page 45 AccuMax SP Installation and Operation Manual Symptom Probable Cause(s) Corrective Action Foam Flowmeter sensor Inspect wiring and connection Pump runs for 8 to 10 seconds circuit open. to foam flowmeter. then shuts down. ERR.HY may be flashed on display. Foam Flowmeter Check to ensure that the positioned incorrect.
  • Page 46 Installation and Operation Manual Symptom Probable Cause(s) Corrective Action System returns to standby mode Poor ground to valve driver box. Make sure screws are tight and while pumping or HYPRO appears a good ground is maintained. momentarily while pumping. Low hydraulic oil pressure. Clean or replace filters.
  • Page 47 AccuMax SP Installation and Operation Manual Symptom Probable Cause(s) Corrective Action System cannot be calibrated. Calibration values selected are out Perform system reset as of range of system or setup memory described in Calibration Section is full. and recalibrate. Cannot enter Calibration Mode. Truck hydraulics and hydraulic valve Make sure hydraulic system is driver is not turned on.
  • Page 48: Specifications

    Installation and Operation Manual Specifications Specifications Contents The following section includes: ● Standard part information ► Standard part identification ..................Page 49 ► Standard part performance ..................Page 50 ► Standard part dimensional information ..............Page 51 ► Hydraulic pump dimensional information ............Pages 52 - 55 ●...
  • Page 49 AccuMax SP Installation and Operation Manual Miscellaneous Standard Components Ref. Part No. Description Ref. Part No. Description 3304-0027 Calibrate/Inject Valve 3020 - 3060 3320-0046 Check Valve 3020, 3040 3304-0026 Calibrate/Inject Valve 3090 3320-0041 Check Valve 3060 3304-0029 Calibrate/Inject Valve 3150 3320-0047 Check Valve 3090 3304-0030...
  • Page 50 Installation and Operation Manual Flowmeter Specifications Sensor Assembly O-Rings *4.00" min. (102 mm) Retaining Ring NOTE #3 Female Pipe Threads *3.12" min. (79 mm) Grooved for pipe NOTES: 1. Use caution not to damage sensor during assembly. 2. Use Loctite ® PST or equivalent Teflon tape to seal pipe threads.
  • Page 51 AccuMax SP Installation and Operation Manual Cutout Dimensions for Display Control Module Display Requires 3-7/8" (98 mm) Diameter Hole 1.04 2.70 3.50 4.25 26.3 68.7 88.9 4.25 3.50 88.9 #10 24 UNC x 7/16 DP (4) Holes for Mounting Cutout Dimensions for Instruction, System, System Spec.
  • Page 52 Installation and Operation Manual Hydraulic Pump 3020 & 3040...
  • Page 53 AccuMax SP Installation and Operation Manual Hydraulic Pump 3060...
  • Page 54 Installation and Operation Manual Hydraulic Pump 3090, 3150...
  • Page 55 AccuMax SP Installation and Operation Manual Hydraulic Pump 3300...
  • Page 56 Installation and Operation Manual Specifications for Fire Lion Pump Systems System Capacity Maximum Water Flow GPM (LPM) Foam Concentrate Rate 3020 3040 3060 3090 3150 3300 2,000 (7571) 4,000 (15,142) 6,000 (22,712) 9,000 (34,069) 15,000 (56,781) 30,000 (113,563) 667 (2525) 1,333 (5046) 2,000 (7,571) 3,000 (11,356)
  • Page 57 AccuMax SP Installation and Operation Manual Fire Lion Hydraulic Fittings and Hose Specifications Connection Model Minimum Hose ID Pump Port Fitting Motor Port Fitting & Type & Pressure Rating 3020/3040 1" Suction #16 SAE O-Ring 3060 1" Suction #16 SAE O-Ring Hydraulic Reservoir to Hydraulic Charge 3090...
  • Page 58 Installation and Operation Manual Fire Lion Pump/Motor Assembly Parts ITEM Part No. Description Qty. 8000-1010 Foam Pump - 3020 8000-1011 Foam Pump - 3040 8000-1012 Foam Pump - 3060 8000-1013 Foam Pump - 3090 8000-1014 Foam Pump - 3150 8000-1015 Foam Pump - 3300 2740-1007 Coupling Half - 3020 Pump...
  • Page 59 Installation and Operation Manual 3020 – Fire Lion Pump/Motor Assembly (P/N 3450-1035) DISCHARGE PORT 1" GROOVED VICTAULIC Ø .56 THRU (4) HOLES 5.25 6.00 3.25 6.50 12.00 10.50 6.75 2.19 SUCTION PORT 1" GROOVED VICTAULIC 3.16 PORT A 1.58 SAE -12 ORB PORTB SAE -12 ORB 7.46...
  • Page 60 Installation and Operation Manual 3060 – Fire Lion Pump/Motor Assembly (P/N 3450-1037) DISCHARGE PORT Ø .56 THRU 1 1/2" GROOVED VICTAUIC (4) HOLES CASE DRAIN SAE -10 ORB (2) PLACES 6.00 5.25 3.88 1.13 2.25 7.75 10.50 12.00 SUCTION PORT 1 1/2"...
  • Page 61 Installation and Operation Manual 3150 – Fire Lion Pump/Motor Assembly (P/N 3450-1039) 10.00 CASE DRAIN 5.00 SAE -10 ORB SUCTION PORT 3" GROOVED VICTAULIC DISCHARGE PORT 3" GROOVED VICTAULIC 10.00 5.25 CASE DRAIN SAE -10 ORB 12.14 18.15 27.67 Ø .55 (6) HOLES 3/4"...
  • Page 62 Installation and Operation Manual Specifications for Edwards Pump Systems System Capacity Maximum Water Flow GPM (LPM) 3020 3040 3060 3090 3150 3300 Foam Concentrate Rate 2,000 (7,571) 4,000 (15,142) 6,000 (22,712) 9,000 (34,069) 15,000 (56,781) 30,000 (113,563) 667 (2,525) 1,333 (5,046) 2,000 (7,571) 3,000 (11,356) 5,000 (18,927)
  • Page 63 Installation and Operation Manual Edwards Hydraulic Fittings and Hose Specifications Connection Model Minimum Hose ID Pump Port Fitting Motor Port Fitting & Type & Pressure Rating 3020/3040 1" Suction #16 SAE O-Ring 3060 1" Suction #16 SAE O-Ring Hydraulic Reservoir to Hydraulic Charge 3090 1"...
  • Page 64 Installation and Operation Manual Edwards Parts Identification Pump/Motor Assembly ITEM Part No. Description Qty. 8000-0075 Foam Pump - 3020 8000-0076 Foam Pump - 3040 8000-0077 Foam Pump - 3060 8000-0078 Foam Pump - 3090 8000-0079 Foam Pump - 3150 8000-0080 Foam Pump - 3300 2740-0014 Coupling Half - 3020, 3040 Pump...
  • Page 65 Installation and Operation Manual 3020 & 3040 – Edwards Pump/Motor Assembly (P/N 3450-0071 & 3450-0072) [663] 26.1 [481] 19.0 [197] [80] [211] [40] 1-1/2" NPT [95] Outlet Port 1-1/2" NPT Inlet Port [127] [83] [248] [181] Port A 1-1/16"-12 Straight Thd Port B O-Ring Port 1-1/6"-12...
  • Page 66 Installation and Operation Manual 3090 – Edwards Pump/Motor Assembly (P/N 3450-0074) Port A 1.0625-12 SAE Str.Thd. O-ring Boss Case Drain 1" Split Flange Boss SAE J518 (Code 62) [83.6] Port B 1" Split Flange Boss [445.59] SAE J518 (Code 62) 17.54 [531.44] 20.92...
  • Page 67 Installation and Operation Manual 3300 – Edwards Pump/Motor Assembly (P/N 3450-0076) 1" SAE Split Flange 1.0625 SAE Str.Thd. Case Port A Outlet [84] 1" SAE Split Flange [489] Port B [248] 19.2 [582] 22.9 [871] 34.3 3" NPT Inlet [614] 24.2 3"...
  • Page 68 Installation and Operation Manual Specifications for Trident Pump Systems System Capacity Maximum Water Flow GPM (LPM) Foam Concentrate Rate 3020 3040 3060 3090 3150 3300 2,000 (7,571) 4,000 (15,142) 6,000 (22,712) 9,000 (34,069) 15,000 (56,781) 30,000 (113,563) 667 (2,525) 1,333 (5,046) 2,000 (7,571) 3,000 (11,356) 5,000 (18,927)
  • Page 69 Installation and Operation Manual Trident Hydraulic Fittings and Hose Specifications Connection Model Minimum Hose ID Pump Port Fitting Motor Port Fitting & Type & Pressure Rating 3090 1" Suction #16 SAE O-Ring Hydraulic Reservoir to Hydraulic Charge 3150 1" Suction #16 SAE O-Ring Pump Inlet 3300...
  • Page 70 Installation and Operation Manual Trident Pump/Motor Assembly Parts ITEM Part No. Description Qty. 8000-1018 Foam Pump - 3020 8000-1019 Foam Pump - 3040 8000-1019 Foam Pump - 3060 8000-1020 Foam Pump - 3090 8000-1021 Foam Pump - 3150 8000-1022 Foam Pump - 3300 2740-1008 Coupling Half - 3020 Pump 2740-1008...
  • Page 71 Installation and Operation Manual 3090 – Trident Pump/Motor Assembly (P/N 3450-1044) 8.00 CASE DRAIN PORT SAE -10 ORB 12.51 9.25 2" VICTAULIC SUCTION PORT 2" VICTAULIC DISCHARGE PORT 5.63 CASE DRAIN PORT SAE -10 ORB PORT A 12.38 3/4" SPLIT FLANGE BOSS SAE J518 (CODE 62) PORT B 10.49...
  • Page 72 Installation and Operation Manual 3150 – Trident Pump/Motor Assembly (P/N 3450-1045) DISCHARGE PORT SUCTION PORT 3" GROOVED VICTAULIC 3" GROOVED VICTAULIC 8.00 4.00 12.51 11.38 7.63 5.66 5.25 13.13 10.50 21.92 31.44 3/4" SAE SPLIT FLANGE PORT PER SAE J518 (CODE 62) (2) PORTS 2.95 1.07...
  • Page 73 Installation and Operation Manual NOTES...
  • Page 74 Installation and Operation Manual NOTES...
  • Page 75 Installation and Operation Manual NOTES...
  • Page 76: Warranty

    Installation and Operation Manual Installation and Operation Manual Limited Warranty Fire Research Corp. (FRC), as supplier of FoamPro, warrants to the original purchaser, each new pump, system or other product of its own manufacture, for a period of two years from the date of shipment from the factory, to be free from defects in material and workmanship under normal use and service.