2-way cassette type super long life filter

Advertisement

Super Long Life Filter
Preparing to install the ceiling panel
Remove the center panel and air filter referring to the Installation Manual of the ceiling panel. (The removed air
filter is not for use.)
Attaching the heat insulator
▼ Figure 6
Installing the ceiling panel
1
Fit the temporary hanging hooks on the
ceiling panel over the hangers on the sides
of the indoor unit. (Figure 7)
When fitting, align the louver motor wire end of the
ceiling panel with the electrical control box end of
the indoor unit. (Figure 7)
2
Confirm that the temporary hanging hooks
on both sides of the ceiling panel are fitted to
the Filter Chamber securely and release your
hands from the panel.
NOTE
When detaching the ceiling panel, detach the frame
covers of the ceiling panel first and lift up the ceiling
panel, then lower the panel slowly, pushing the knobs of
the temporary hanging hooks in the direction of the arrow
shown in Figure 7.
7-EN
Installation Manual
Attach the heat insulator (11)
Complete image
(use 2 insulators for 283UW, and
4 for 803UW and 1403UW)
▼ Figure 7
Ceiling panel
Temporary
Louver motor
hanging hook
Temporary
wiring
hanging
hook
Temporary
Indoor unit
hanging hook
Filter Chamber
Ceiling panel
Hanger on the
indoor unit
(equipped on
Knob of the
both sides)
temporary
hanging hook
Frame cover
Push in the direction of the
arrow when detaching the
ceiling panel.
Super Long Life Filter
3
Confirm that the screw holes on the ceiling
panel and the indoor unit are aligned and fix
the panel to the indoor unit with the supplied
screws (M5 x 40mm: 4 screws for UW283PG
and UW803PG, 6 screws for UW1403PG).
(Figure 8)
NOTE
• Make sure that none of the wiring is pinched before
fixing the screws.
• The screws are taped to the foamed polystyrene
packaging of the ceiling panel.
4
Confirm that there are no gaps between the
indoor unit and the Filter Chamber, between
the Filter Chamber and the ceiling panel, or
between the ceiling panel and the surface of
the ceiling. (Figure 9)
CAUTION
• Tighten the screws enough to prevent the problems
shown in the illustration below.
Air leaking
Air leaking from
the ceiling
Accumulation of dirt
Condensation, water leaking
– 4 –
Installation Manual
▼ Figure 8
Filter Chamber
Electrical control box
Indoor
unit
Ceiling
panel
For UW1403PG, the center
is also fixed using two
additional screws.
Screws (M5 x40L: accessary parts
of the ceiling panel)
▼ Figure 9
Filter Chamber
No gap
Indoor unit
Surface of the ceiling
Ceiling panel
• Adjust the height of the indoor unit if gaps remain
between the ceiling and the ceiling panel after
tightening the screws.
Fix level with no gaps.