4.2
Installing a PE Cable
•
It is recommended that the
PE cable of the solar inverter
be connected to a nearby
ground point. Connect the PE
points of all solar inverters in
the same array to ensure
equipotential connections to
PE cables.
•
To enhance the corrosion
resistance of a ground
terminal, you are advised to
apply silica gel or paint on it
after connecting the PE cable.
Opening the Maintenance Compartment Door
4.3
•
Do not open the panel of the solar inverter.
•
Before opening the maintenance compartment door, turn off the downstream AC output
switch and three DC switches at the bottom.
•
Do not open the maintenance compartment door in rainy or snowy days. If you have to, take
protective measures to prevent rain or snow from entering the maintenance compartment.
•
Do not leave unused screws in the maintenance compartment.
1. Loosen the screws on the
maintenance compartment door.
2. Open the maintenance compartment door and
adjust the support bar.
8
Reserved PE point