Kohler 15REYG Installation Manual page 38

Commercial generator sets
Hide thumbs Also See for 15REYG:
Table of Contents

Advertisement

then step through the following parameters. Use the up
(
) and down (
) arrow buttons to select the appropriate
setting for the application.
Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.
Voltage/frequency setting (Uu). Select the system
voltage and frequency from the table in Figure 5-1.
Note: This parameter sets the nominal system voltage
and frequency. To adjust the output (measured)
voltage, see Section 5.1.
Unit configuration (Uc).
generator set type. Select Uc01, standby.
Engine configuration (Ec). The engine configuration
must match the generator set engine type.
Parameter
Unit's system voltage
and frequency
Unit configuration
Engine type
Engine data input types
Battery voltage
Communications
CANbus address
* ADC application program version 3.25 or higher is required
Figure 5-1 Configuration Parameters
38
Section 5 Controller
This parameter sets the
Voltage, VAC
Setting
Uu01
120/240
Uu04
277/480
Uu10
120/240
Uu10
139/240
Uu11
120/208
Uu16
127/220
Uc01
Standby
Ec11 *
30REYG
Ec12 *
15REYG
Ed01
15/30REYG factory setup
Bt12
12 VDC
Cn00
No CAN communications, 48-hour power down (factory setting)
Cn01
J1939 communications, no power down
Cn06
Enables J1939 communications and 1-hour ADC power down after engine stop
for either:
a. Remote start/stop switch
b. Automatic transfer switch
CA01
15/30REYG
Advanced configuration mode (Adnc). The data
input types, battery voltage, and communications
setting can be changed in the advanced configuration
mode.
Press the up arrow button when Adnc is
displayed to enter the advanced configuration mode.
Engine data input types (Ed). This setting defines the
type of senders used on the generator set engine.
Battery voltage (Bt). This setting toggles between 12
and 24 VDC for the engine starting battery voltage.
Communications setting (Cn). This setting allows the
user to set the controller for communication with
optional meters. The factory setting is Cn00, no CAN
communications. Change this setting if necessary. See
Figure 5-1.
CANbus address (CA).
CANbus address for the controller. The CA parameter
appears only on models with engines equipped with
ECMs.
Description
Frequency, Hz
Phases, Wires
60
Single phase, 3 wire
60
Three phase, 4 wire
60
Three phase, 4 wire
60
Three phase, 4 wire
60
Three phase, 4 wire
60
Three phase, 4 wire
This parameter sets the
Connection
1 phase
Wye
Delta
Wye
Wye
Wye
TP-6727 10/11

Advertisement

Table of Contents
loading

This manual is also suitable for:

30reyg

Table of Contents