Page 2
3 29.01.99 PKV 30-IBS 9715001 revision Although this appliance has been developed with great care and intensively tested, Hilscher Gesellschaft für Systemautomation mbH cannot guarantee the suitability of this appliance for any purpose not confir- med by us in writing.
The protocol converter PKV 30-IBS has two communications interfaces and one of them is for the remote bus InterBus and the other one is for the connection of the external decive to the PKV 30-IBS. These interface could be also used for diagnostic.
Valid operation and an error state from the serial interfaces are displayed by LEDs. Block diagram of the protocol converter PKV 30-IBS Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
Side viewing of PKV 30-IBS with jumper row selection jumper J2 interface open RS232 RS485 1-2, 3-4 RS422 4 3 2 Selection of serial interface type Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
3-way COMBICON plug from PHOENIX (MSTB 2.5/3-ST-5.08) is used. symbol signal +24V +24V supply voltage reference potential earth ground Pin assignment of the X1 power supply connector Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
C13A P9715S21.HP 15n/630V Circuit of the 'Remote IN' interface at connector X2 of PKV 30-IBS The shield of the connector is connected to the earth ground of the PKV 30-IBS over a RC combination (1 MOhm, 15 nF). Signal Symbol...
General device description 2.3.2 Remote bus interface 'Remote OUT' The PKV 30-IBS has these fieldbus interface connection to connect the bus cable to the next slave. A 9 way D-Sub female connector is used. The next picture shows the scematic of the interface. The interface is not isolated by optocouplers 2.7k...
ü output ready to send ü input clear to send ü input RXD-N receive data inverted RS 422 Pin assignment of the serial device interface X4 Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
The PC is connected by a three-way cable which must not be longer than 15 m. The wiring of the cable is shown below. Diagnostic cable between the protocol converter and the PC Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
If the message Connection could not be established or connection lost appears, then try to activate the dia- gnostic/configuration mode again according to the steps described above. Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
2.5 Status displays - LED On the PKV 30-IBS there are two groups of state LEDs. One group displays the state of the PKV 30-IBS device and the other group shows the state of the Inter- Bus slave. 2.5.1 Device display...
'Remote bus OUT' disabled interface 'Remote bus OUT' enabled green PCP data telegramms active no PCP data telegramms active Meaning of the different state LEDs of the PKV 30-IBS Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
Connector arrangement on the protocol converter Physical dimensions of the protocol converter for snap mounting to a mounting rail The overall height of the converter is approx. 80 mm. Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
18V - 30V, max. 0.15 A at 24 V Operating temperature 0 to 50 degrees Celsius Safety type IP50 Dimensions (LxHxD) 105 x 105 x 80 mm Mounting rail mounting DIN EN 50022 Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49 (0) 6190/9907-99 * De:P30IBS#3E...
Need help?
Do you have a question about the PKV 30-IBS and is the answer not in the manual?