7.1 Errors / Diagnostics display

All measurement values are stored twice with the accompanying checksums. In case the checksum fails, the backup
data is used. If both the normal storage and backup fail, the meter will stop working and indicate error XX:
XX is the hexadecimal data, convert the data to binary to analyze the data.
bit0: The data in the main storage area and backup area of the battery is wrong or cannot be operated .
bit1: The battery mantissa area cannot be operated.
bit2: The battery backup area cannot be operated.
bit3: The main battery storage area cannot be operated .
bit4: Data error in the battery mantissa area.
bit5: Data error in the battery backup area (integer bit).
bit6: Data error in the main battery storage area (integer bit).
bit7: EEPROM cannot be fully initialized.