WAGO 4PS User Manual

WAGO 4PS User Manual

Energy meters with push-in-cage clamp and levers

Advertisement

Quick Links

WAGO Energy Meters (MID)
with Push-in-CAGE CLAMP® and Levers
879-3020
User manual
Version: 052021V1.1
© 2021 Wago. All rights reserved.
4PS
879-3000
4PU

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 4PS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for WAGO 4PS

  • Page 1 WAGO Energy Meters (MID) with Push-in-CAGE CLAMP® and Levers 879-3020 879-3000 User manual Version: 052021V1.1 © 2021 Wago. All rights reserved.
  • Page 2: Table Of Contents

    4.5 Modbus/RS485 communication specification........................... 8 4.6 Dimensions ......................................9 4.7 Wire connection ....................................9 4.8 Connection diagram 879-3000 (4PU) ..............................10 4.9 Connection diagram 879-3020 (4PS) ..............................11 5 Installation ....................................12 6 Operation ....................................13 6.1 Display part 1 (MID relevant) ................................13 6.2 Display part 2 (MID relevant) ................................
  • Page 3: Safety Instructions

    Use for the intended perpose This device may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by Wago. Proper handling The prerequisites for perfect, reliable operation of the product are proper transport, storage, installation and connection, as well as proper operation and maintenance.
  • Page 4 The data in this manual are checked regularly and the necessary corrections will be included in subsequent editions. If you have any suggestions, please do not hesitate to contact us. 4- 4PU & 4PS - Wago...
  • Page 5: Foreword

    Therefore NEVER open an energy meter or break the seal of the device. The limited warranty is 5 years after production date, divided into various periods., after production, and only valid for production faults. Wago - 4PU & 4PS - 5...
  • Page 6: Certificates

    3 Certificates 6 - 4PU & 4PS - Wago...
  • Page 7: Specifications

    (Feindrähtiger Leiter/Fine-stranded conductor) 37 A 25 A 4 mm² 32 A (Feindrähtiger Leiter mit Aderendhülse/ 27 A Fine-stranded conductor with insulated ferrule) 17 A 4 mm² 30 A (Feindrähtiger Leiter/Fine-stranded conductor) 25 A 15 A Wago - 4PU & 4PS - 7...
  • Page 8: Basic Errors

    *Note that the maximum number of meters is dependent on the converter, baudrate (the higher the baudrate, the smaller the number of meters which can be used) and the circumstances under which the meters are installed. 8 - 4PU & 4PS - Wago...
  • Page 9: Dimensions

    Push-in technology can be used for Solid conductors and fine-stranded conductors with insulated ferrule. Fine-stranded conductors require opening the levers for connection. Wiring diagram: Solid conductor Fine-stranded conductor Wiring diagram: with insulated ferrule Wiring diagram: Fine-stranded conductor Wago - 4PU & 4PS - 9...
  • Page 10: Connection Diagram 879-3000 (4Pu)

    Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC) 10 - 4PU & 4PS - Wago...
  • Page 11: Connection Diagram 879-3020 (4Ps)

    Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC) Wago - 4PU & 4PS - 11...
  • Page 12: Installation

    In case the meter is installed in an area with frequent surges for example due to thunderstorms, welding machines, inverters etc., the meter is required to be protected with a Surge Protection Device. • The device should be sealed immediately after installing it in order to prevent tampering. 12 - 4PU & 4PS - Wago...
  • Page 13: Operation

    Scroll through the display pages (Total - L1 - L2 -L3) using the capacitive touch buttons on the frontside of the meter. Wago - 4PU & 4PS - 13...
  • Page 14: Settings

    Now the Bluetooth ist activated in the energy meter and you can scan the QR code on the display or scan the area for bluetooth devices by using the wago mobile phone app. 14 - 4PU & 4PS - Wago...
  • Page 15: Button Settings

    When Bluetooth connection is active, the Bluetooth activation icon will be show on the display: Go to Appendix 4 - Bluetooth for the wago mobile phone app user guide. 6.6 Button settings Settings can also be done using the capacitive touch buttons on the front of the meter. Scroll through the options using the left <<...
  • Page 16: Password

    For this external voltage source, the voltage (Ui) should be lower than 27V DC. The maximum switching current (Imax) is 100mA. To connect the impulse output, connect 5-27V DC to connector 4/6 (collector), and the signal wire (S) to connector 5 (emitter). Beispiel Verdrahtung der S0-Impulskontakte 16 - 4PU & 4PS - Wago...
  • Page 17: Pulse Type Setting

    The default S0 pulse width is 30ms. The pulse width setting can be modified to 2-99ms (depending on the imp/kWh setting). 6.6.6 Modbus ID The Modbus ID can be set from 1 to 247, the default Modbus ID is 1. Wago - 4PU & 4PS - 17...
  • Page 18: Modbus Baudrate

    6.6.10 M-Bus baud rate The default M-bus baud rate setting is 2400. The M-Bus baud rate setting can be modified to: 9600 / 4800 / 2400 (default) / 1200 / 600 / 300 bps. 18 - 4PU & 4PS - Wago...
  • Page 19: Backlight

    6.6.13 Trip counter The meter is equipped with a trip counter that can be set to zero by the user. This is the energy calculated based on the combination code setting (see 6.6.15). Wago - 4PU & 4PS - 19...
  • Page 20: Obis Codes

    44.7.0 (reverse -) 63.7.0 (forward +) ; L3 Reactive power 64.7.0 (reverse -) 11.7.0 Current 31.7.0 L1 Current 51.7.0 L2 Current 71.7.0 L3 Current 32.7.0 L1 Voltage 52.7.0 L2 Voltage 72.7.0 L3 Voltage 20 - 4PU & 4PS - Wago...
  • Page 21: Combination Code (Adjustable Via Modbus, M-Bus & Bluetooth)

    +5 kWh -12 kWh LCD reading and calculation of total energy Code C-01 C-02 C-03 C-04 C-05* Total Forward Reverse *Meters ordered or set afterwards to C-05 cannot be set to another calculation mode. Wago - 4PU & 4PS - 21...
  • Page 22: Troubleshooting

    5-27V DC should be connected to the collector connection (pin 4/6) and the signal wire to the emitter connection (pin 5). If none of the above works, please contact technical support 22 - 4PU & 4PS - Wago...
  • Page 23: Errors / Diagnostics Display

    EEPROM cannot be fully initialized. 7.2 Technical support For questions about one of our products please contact our technical support: Telefon: +49 (0) 571/887 – 44555 Fax: +49 (0) 571/887 – 844555 E-Mail: support@wago.com Website: www.wago.com/support Wago – 4PU & 4PS - 23...
  • Page 24: Appendix 1 - Multi Tariff Function

    T3 and T4 can only be activated by Bluetooth, Modbus, M-bus or using the button function. After activating T3 and/or T4 once, the energy values per tariff (3 / 4) will be displayd in the MID relevant part of the display. This cannot be undone. 24 – 4PU & 4PS - Wago...
  • Page 25: Appendix 2 - M-Bus

    Appendix 2 - M-Bus A2.1 Communication via M-Bus The 4PU and 4PS meters are equipped with an M-bus port, the data can be read out via this port. The communication protocol conforms to the EN13757-3 standard. The meter can communicate with your PC. In order to read out the meter registers first install and configure the PC software. Use an M-bus level converter to connect the PC and the meter.
  • Page 26: A2.2 M-Bus Register Map

    FD 3A 00 01 1,00 Grid frequency FB 2C 37 C7 00 50,999Hz Tariff 7C 01 54 CT rate (only for CT version) FD 3A 05 95 99 9995/5 Checksumme xx xx xx 16 26 - 4PU & 4PS - Wago...
  • Page 27: A2.3 M-Bus Write Registers

    Manufacturer ID Generation version Medium 68 0B 0B 68 53 FD 52 aa aa aa aa bb bb Input 01 00 07 13 CD 25 Remarks 13070001 Major version of the software Electricity 27 - 4PU & 4PS - Wago...
  • Page 28: Appendix 3 - Modbus

    For the registers used in the meter and how to interpreted the data, please use the Modbus register map on the next pages. More information on Modbus can be found: Physical: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf Protocol: http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf Wago - 4PU & 4PS - 28...
  • Page 29: A3.2 Modbus Register Map

    Content Function code Length Unit Data type 4000 Serial number 4002 Meter code 4PU: 1111 - 4PS: 1112 - 2PCT: 1113 4003 Modbus ID Signed 4004 Baud rate Signed 1: 300 - 2: 600 - 3: 1200 - 4: 2400...
  • Page 30 502C L1 Power factor Float ABCD 502E L2 Power factor Float ABCD 5030 L3 Power factor Float ABCD 5032 L1-L2 Voltage Float ABCD 5034 L1-L3 Voltage Float ABCD 5036 L2-L3 Voltage Float ABCD Wago - 4PU & 4PS - 30...
  • Page 31 Float ABCD 603A L3 Forward reactive energy kvarh Float ABCD 603C Reverse reactive energy kvarh Float ABCD 603E T1 Reverse reactive energy kvarh Float ABCD 6040 T2 Reverse reactive energy kvarh Float ABCD 31 - 4PU & 4PS - Wago...
  • Page 32 Exp. Inductive reactive energy in Q3 (T3) Float ABCD 607F Exp. Inductive reactive energy in Q3 (T4) Float ABCD 6081 Exp. capacitive reactive energy in Q4 (total) Float ABCD 6083 Exp. capacitive reactive energy in Q4 (T1) Float ABCD Wago - 4PU & 4PS - 32...
  • Page 33 Float ABCD 6089 Exp. capacitive reactive energy in Q4 (T4) Float ABCD 608B Resettable day counter L1 Float ABCD 608D Resettable day counter L2 Float ABCD 608F Resettable day counter L3 Float ABCD 33 - 4PU & 4PS - Wago...
  • Page 34: A3.3 Modbus Write Register

    01 06 4032 0001 (new setting: turn 180 0: standard - 1: turn 180 degrees degrees) 4033 OBIS code ON/OFF 0 = Signed Command: 01 06 4033 0001 (new setting: OBIS ON) 0: OFF - 1: ON Wago - 4PU & 4PS - 34...
  • Page 35: Appendix 4 - Bluetooth

    All Push-in-CAGE CLAMP® meters are able to be read and configured via Bluetooth. The standard used is standard used is BLE 4.2. You can download the smartphone app for Android and IOS free of charge from the stores. You can find the smartphone app under the name "WAGO Energy Meter Configurator". A4.1 Bluetooth app Activate the Bluetooth on the energy meter according to the steps in 6.5 Bluetooth.
  • Page 36: A4.2 Connect The Meter

    Select the correct serial number for the connection. 2. Scan QR: The app opens the camera of the cell phone to scan the QR code on the meter display. Once the code is scanned, the meter is connected. Wago - 4PU & 4PS - 36...
  • Page 37: A4.3 Device Page

    A4.3 Device page The energy meter is now connected to the smartphone app. The meter type, serial number, software version and checksums are displayed on the device page. 37 - 4PU & 4PS - Wago...
  • Page 38: A4.4 Read Meter Data

    A4.4 Read meter data All energy values are located under "Energy", as well as all instantaneous values are located under "Instantaneous". Refresh the data using the refresh arrow in the upper right corner. Wago - 4PU & 4PS - 38...
  • Page 39: A4.5 Save Meter Data

    Save the data using the memory disk in the upper right corner. The data can be stored locally on the smartphone or shared through various channels such as email, Bluetooth or other programs. 39 - 4PU & 4PS - Wago...
  • Page 40: A4.6 Change Settings

    Save the values via the memory disk in the upper right corner. First, a pop-up menu for the password appears. By default, the password is always 0000. The password can only be changed on the meter using the keys. After entering the correct password, the new settings are saved in the meter. Wago - 4PU & 4PS - 40...
  • Page 41 WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH. “Copyright - WAGO Kontakttechnik GmbH & Co. KG - All rights reserved. The content and structure of the WAGO websites, catalogs, videos and other WAGO media are subject to copyright. The distribution or modification of the content of these pages and videos is not permitted.