Periodic maintenance of the system
For perfect effi ciency of the fi re detection system, the customer shall provide for a preventive maintenance program. The
frequency of inspections depends on several factors; it is recommended to perform an inspection on average every 6 months
(unless specifi cally required otherwise). Maintenance should be carried out by specialized personnel provided with the necessary
know-how and equipment to perform adequate maintenance work. It is assumed that the information needed to perform a proper
maintenance can be provided by the designers and/or manufacturers the fi re detection system.
The maintenance guidelines are provided in the Italian standard UNI 11224.
The most signifi cant checks should include at least:
Functional state of power supply units and accumulators (APS) of the control panel and of the system power supply modules.
State of the batteries of the self-powered devices (sirens, communicators).
Functional tests of the sensors that make up the system.
Checks about the state of cleanliness of the analysis chambers of the optical sensors.
Effi ciency of the control organs of the control panel and repeaters.
Functional and operational effi ciency of the acknowledgement, evacuation and system recovery procedures.
Effi ciency of manual alarm button module.
Effi ciency of optical and acoustic notifi cation module.
Effi ciency of phone communicators (phone call tests).
Verifi cation of system actuations entrusted to input and output interface modules, etc.
Check for correct tightening of the terminals wires.
Final drafting of a test report signed by the maintainer and by the customer for acceptance.