Plug-in detector base

Advertisement

Quick Links

REMOTE ANNUNCIATOR, MODEL RA400Z
The remote annunciator is connected between terminals 1 and 3 using the spade lug terminal packed with the remote
annunciator. The spade lug terminal is connected to the base terminal as shown in Figure 5.
It is not acceptable for three stripped wires to be under the same wiring terminal unless they are separated by a
washer or equivalent means. The spade lug supplied with the model RA400Z is considered an equivalent means. See
Figure 5 for proper installation.
STRIPPED WIRE
WIRE WITH
SPADE LUG
C0116-00
Figure 5: Connection to Remote Annunciator Terminal
Please refer to insert for the Limitations of Fire Alarm Systems
N550-05-00
www.PDF-Zoo.com
4
I56-637-06R
©2003 Notifier
Before installing detectors, please thoroughly read the system wiring and installation manuals, and manual System
Smoke Detectors Application Guide, which provides detailed information on detector spacing, placement, zoning, and
special applications. Copies of these manuals are available from Notifier.
GENERAL DESCRIPTION
The B710LP base is a plug in detector base intended for use in a 2-wire intelligent system, with screw terminals provided
for power (+ and –), and remote annunciator connections. Communication takes place over the power (+ and –) lines.
BASE TERMINALS
NO.
FUNCTION
1
POWER (–), REMOTE ANNUNCIATOR (–)
2
POWER (+)
3
REMOTE ANNUNCIATOR (+)
SPECIFICATIONS
Diameter:
Mounting:
Operating Temperature Range:
N550-05-00
firealarmresources.com
B710LP Plug-in Detector Base
Installation Instructions
TAMPER PROOF
TAB
BASE
TERMINALS
2
1
3
Figure 1: Terminal Layout
6.1 inches (15.5 cm)
4-inch square box (102 mm) with or without plaster ring
Min. Depth: 1.5 inches (38 mm)
4-inch (102 mm) Octagon Box, Min. Depth: 1.5 inches (38 mm)
3-1/2 inch (89 mm) Octagon Box, Min. Depth: 1.5 inches (38 mm)
Single Gang Box, Min. Depth: 1.5 inches (38 mm)
32° to 150°F (0° to 66°C)
1
Notifier, 12 Clintonville Rd., Northford , CT 06472-1653, (203) 484-7161
C0127-00
I56-637-06R

Advertisement

loading
Need help?

Need help?

Do you have a question about the B710LPA and is the answer not in the manual?

Questions and answers

Summary of Contents for Notifier B710LPA

  • Page 1 STRIPPED WIRE Smoke Detectors Application Guide, which provides detailed information on detector spacing, placement, zoning, and special applications. Copies of these manuals are available from Notifier. GENERAL DESCRIPTION The B710LP base is a plug in detector base intended for use in a 2-wire intelligent system, with screw terminals provided for power (+ and –), and remote annunciator connections.
  • Page 2 MOUNTING ELECTRICAL RATINGS — includes Base and Detector REMOTE ANNUNCIATOR CAUTION: Do not loop wire under terminal 1 or 2 This detector base mounts directly to 3-1/2 inch and 4 Voltage Range: 15 – 32 Volts DC Peak Break wire run to provide supervision of connections. inch octagon boxes, 4 inch square boxes (with or without Standby Current (nominal): 150 µA at 24 VDC...

This manual is also suitable for:

B710lp