Notifier B614LP Installation Instructions
Notifier B614LP Installation Instructions

Notifier B614LP Installation Instructions

Plug-in detector base

Advertisement

Quick Links

FOR USE WITH THE FOLLOWING SMOKE DETECTOR MODELS:
IN US:
CP-651, SD-651
IN CANADA:
CP-651A, SD-651A
IN EUROPE:
CP-651E, SD-651E
Before installing detectors, please thoroughly read manual I56-407-01, Guide for Proper Use of System Smoke
Detectors , which provides detailed information on detector spacing, placement, zoning, wiring, and special appli-
cations. Copies of this manual are available at no charge from Notifier. (For installation in Canada, refer to CAN/
ULC-S524-M86, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 re-
quirements. The detector used with this base should be cleaned at least once a year.

GENERAL DESCRIPTION

The model B614LP detector base is designed for use with Notifier model SD-651, SD-651A, and SD-651E photo-
electronic detector heads and CP-651, CP-651A, and CP-651E ionization detector heads. This four-wire base is
equipped with screw terminals for the connection of power, ground, relay connections, and an optional remote
annunciator. It also includes a resistor that limits current when the associated smoke detector is in the alarm state.

BASE TERMINALS

No.
Function
1
Remote Annunciator (+)
2
Not used
3
Not used
4
Remote Annunciator (-)
5
Not used
6
N.O.
Supervisory Relay
}
7
N.O
Form A Contacts
8
N.O.
Alarm Relay
}
9
N.O.
Form A
10
C.
Initiation
11
C.
Contacts
12
N.O.
Alarm Relay
}
13
N.C.
Form C
14
C.
Auxiliary Contacts

SPECIFICATIONS

Base Diameter:
Base Height:
Weight:
Operating Temperature Range:
Operating Humidity Range:
N550-03-00
www.PDF-Zoo.com
B614LP PLUG-IN DETECTOR BASE
INSTALLATION INSTRUCTIONS
6.2 inches (157 mm)
0.95 inches (24 mm)
0.6 lb. (274 g)
4-inch square box with or without plaster ring. Min. depth–1.5 inches
4-inch octagon box. Min. depth–1.5 inches
0° to 49°C (32° to 120°F)
10% to 93% Relative Humidity, Noncondensing
Notifier, 12 Clintonville Rd., Northfield , CT 06472-1652 (203) 484-7161
firealarmresources.com
Figure 1. Terminal Layout
1
I56-647-01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the B614LP and is the answer not in the manual?

Questions and answers

Summary of Contents for Notifier B614LP

  • Page 1 Detectors , which provides detailed information on detector spacing, placement, zoning, wiring, and special appli- cations. Copies of this manual are available at no charge from Notifier. (For installation in Canada, refer to CAN/ ULC-S524-M86, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.) NOTICE: This manual should be left with the owner/user of this equipment.
  • Page 2 ELECTRICAL RATINGS - includes base and detector System Voltage: 120 VAC, 60 Hz Relay Contact Ratings: Resistive or Inductive (60% power factor) load Form A: 2.0A @ 30VAC/DC Form C: 2.0A @ 30VAC/DC SNAP ON DECORATIVE 0.6A @ 110VDC RING 1.0A @ 125VAC Start-up Time: 36.0 Seconds Maximum...
  • Page 3 Figure 3. Wiring Diagram for a Typical 120VAC Detector System WIRING INSTRUCTIONS NOTE: Refer the manufacturer’s instructions for releasing device wiring. NOTE: To ensure that electrical connections are supervised, DO NOT loop wires under terminals 8, 9, 10, and 11 –...
  • Page 4 10 years. The smoke detector system that this detector is used in must be tested regularly per NFPA 72. This smoke detector should be cleaned regularly per NFPA 72 or at least once a year. N550-03-00 I56-647-01 © Notifier 1993 www.PDF-Zoo.com firealarmresources.com...