5.3.2 Example Application Program 2
In current input mode, the 2AD converts analog values from 4 ~ 20mA to the digital output of 0 ~ 2000. If
using a digital range of 4000 ~ 20000 in the program, the range must be converted from 0 ~ 2000 to 4000
~ 20000 as shown in the programming example below. Digital values that are converted from analog
values are stored in D8112 or D8113.
The analog input does not have exact resolution of 8 μA because the digital value is converted from a
range of 0 ~ 2000 to 4000 ~ 20000.
20000
Digital value
used in user
4000
program (D60)
0
Digital value from A/D converter (D8112,D8113)
If a digital value in the range of 4000 ~ 20000 is used in D60, please see below.
Digital value used in user program: D60 = 8 × (D8112 or D8113) + 4000
The program example based on the equation above is as shown in the figure below. (In Ch2 case))
M8000
FNC 22
MUL
FNC 20
D
Attention
This product is designed for use in industrial applications.
Note
Authorized Representative in the European Community:
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
0
M8113
K8
D8113
D62
K4000
ADD
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
Manual number : JY992D96201
Manual revision : D
Date
Digital value from
A/D converter
(D8112,D8113)
2000
D62
D60
: April 2015
2000
0
0
4mA
20mA
Analog input