• Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (the remote controller, removing
the air filters, placing or removing the remote controller from the remote controller holder, cleaning methods, precautions for
operation, etc.)
• Recommend that the user read the OPERATING INSTRUCTIONS carefully.
Model Name
Operating Range
Power Supply
Voltage/Frequency/Phase V/Hz/-
Compressor
Electrical Data
Refrigerate Line
Factory Charge Refrigerant/Oz
Maximum Line Length Ft / m
• The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland waterways. If
the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland waterways, please follow the
installation instruction below.
• Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can damage
the outdoor unit.
Sea breeze
Sea
• If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around it to block the sea breeze.
Protection walls
Sea breeze
Sea
• Install the outdoor unit in a place where water can drain smoothly.
• If you cannot find a place satisfying above conditions, please contact manufacturer. Make sure to clean the sea water and the
dust on the outdoor unit heat exchanger.
PAGE 8

Section 7 - Explaining Operation to the End User

Section 8 - System Specifications
Outdoor
HSU09VHG(DB)-W
Indoor
HSU09VHG(DB)-G
Cooling °F(°C)
Heating °F(°C)
Compressor Type
Maximum Fuse Size A
Minimum Circuit Amp A
Connections
Liquid O.D. in
Suction O.D. in
Maximum Height Ft / m

Section 9 - Seacoast Application

ODU
ODU
• A protection wall should be constructed with a solid material such as
concrete to block the sea breeze and the height and the width of the wall
should be 1.5 times larger than the size of the outdoor unit. Also, secure
ODU
over 28 in (700mm) between the protection wall and the outdoor unit for
exhausted air to ventilate.
ODU
HSU12VHG(DB)-W
HSU12VHG(DB)-G
41~115(5~46)
41~115(5~46)
5~75(-15~24)
5~75(-15~24)
208-230/60/1
208-230/60/1
DC Inverter Driven Rotary
15
15
12
14
Flare
Flare
1/4
1/4
3/8
3/8
R410A/35.3
R410A/38.1
50/15
50/15
33/10
33/10
Sea breeze
Sea
INSTALLATION
HSU18VHH(DB)-W
HSU24VHG(DB)-W
HSU18VHH(DB)-G
HSU24VHG(DB)-G
41~115(5~46)
41~115(5~46)
5~75(-15~24)
5~75(-15~24)
208-230/60/1
208-230/60/1
20
25
17
19
Flare
Flare
1/4
3/8
1/2
5/8
R410A/54.7
R410A/74.1
83/25
83/25
50/15
50/15
ODU