Stop operation
1
Set the rotary switches on the interface P.C. board of the outdoor unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
[A]
[U1]
Interface P.C. board
SW04
SW05
SW15
Push switch
D600 D601 D602 D603 D604
SW06
SW07
SW09
SW10
SW01
SW02
SW03
SW11
SW12 SW13
SW14
SW16
SW17
SW30
EN-71
7-segment display
[B]
[
]
Push switch
SW04
SW05
SW15
7-segment
7-segment
display [A]
display [B]
D600 D601 D602 D603 D604
SW01
SW02
SW03
Rotary switches
9

Troubleshooting

In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit
by checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Set every dip switch to OFF after checking.
7-Segment display and check code
Rotary switch setting
value
SW01
SW02
SW03
1
1
1
Outdoor unit check code
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary code
for one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
E06
Number of indoor units which received normally
E07
E08
Duplicated indoor addresses
E15
E16
00: Capacity over
01 or more: No. of connected units
01: Other line outdoor connected
E20
02: Other line indoor connected
E31
IPDU quantity information*1
F04
F06
F07
F08
F12
F13
F15
F16
F23
F24
F31
H01
– 36 –
Installation Manual
D600
D601 D602 D603 D604
Indication
LED
A
Outdoor unit number
A
(U1)
B
Check code display*
Check code name
Decrease of number of indoor units
Indoor / Outdoor communication circuit error
Duplication of indoor addresses
No indoor unit during automatic addressing
Number of connected capacity over / indoor units
Other line connected during automatic addressing
IPDU communication error
TD sensor error
TE sensor error
TL sensor error
TO sensor error
TS sensor error
TH sensor (Board installed) error
Outdoor temp. sensor miswiring (TE, TL)
Outdoor pressure sensor miswiring (Pd, Ps)
Ps sensor error
Pd sensor error
Outdoor EEPROM error
Compressor breakdown
B
EN-72