Century COMFORT-AIRE VMH-SG Series Service Manual page 105

Single zone mini-splits
Table of Contents

Advertisement

Service Manual - VMHxxSG
TS10-S: Over voltage or too low voltage protection diagnosis and solution
Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit.
Recommended parts to prepare:
• Power supply wires
• IPM module board
• PCB
• Reactor
Troubleshooting and repair:
is the voltage between P and N is around
DC 310V, 340V or 380V? When start up
Note: For certain models, outdoor PCB could not be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.
Check the power supply.
Is it in working order?
YES
Check the connections and wires.
Are they in working order?
YES
Power on and measure the
voltage between P and N.
While the unit is in standby,
the unit, is it in 220V~400V?
YES
Check the reactor.
Is it in working order?
YES
Replace the reactor.
Troubleshooting
Troubleshooting
NO
Turn off the unit.
Ensure proper connections or
NO
replace the wires.
NO
Replace the IPM board.
NO
Replace outdoor PCB.