Delta OHM HD45 Series Manual page 34

Hide thumbs Also See for HD45 Series:
Table of Contents

Advertisement

Relay outputs
P#
DESCRIPTION
085
Ppm threshold for CO
HD46 models with simplified mode
enabled.
086
Temperature relay threshold (X10)
in HD46 models with simplified
mode enabled.
087
Humidity relay threshold (X10) in
HD46 models with simplified mode
enabled.
088
Minimum possible threshold in ppm
for CO
relay in HD46 models with
2
simplified mode enabled.
089
Minimum possible threshold (x10)
for
temperature relay
models
with
enabled.
090
Minimum possible threshold (x10)
for humidity relay in HD46 models
with simplified mode enabled.
091
Minimum possible threshold in ppm
for CO
relay in HD46 models with
2
simplified mode enabled.
092
Maximum possible threshold (x10)
for temp. relay in HD46 models
with simplified mode enabled.
093
Maximum possible threshold (x10)
for humidity relay in HD46 models
with simplified mode enabled.
(3) The displayed value for temperature and humidity is the quantity value multiplied by 10 (decimal
point not displayed).
(4) The parameter measuring unit is the same as the respective measured quantity, set with P#006
and P#007 parameters.
(5) This parameter is for HD45 models.
(6) In HD45 models with relay, if the hardware threshold selector is in position other than 0, the relay
operates only with threshold set via hardware, A and B thresholds are not taken into account.
In HD46 models, if the simplified mode is enabled, relays operate with P#085, P#086 and P#087
thresholds. A and B thresholds are not taken into account.
MODBUS-RTU RS485 serial communication
P#
DESCRIPTION
058
RS485 address
059
RS485 Baud rate
060
RS485 transmission mode
Data Bits = 8
Parity:N= none, E= even, O= odd
Stop Bits: 1= 1bit, 2= 2 bit
061
Receiving mode after RS485
transmission
relay in
2
in
HD46
simplified
mode
- 34 -
VALUE
Over the whole range
Over the whole range
Over the whole range
Over the whole range
Over the whole range
Over the whole range
Over the whole range
Over the whole range
Over the whole range
VALUE
MIN: 1
MAX: 247
0: 9600
1: 19200
0: 8 N 1
1: 8 N 2
2: 8 E 1
3: 8 E 2
4: 8 O 1
5: 8 O 2
0: do not respect protocol
and starts receiving after
transmission
1: respects the protocol and
waits for 3,5 char. after
transmission
DEFAULT
NOTE
800
(6)
210
(3),(4)
(6)
500
(3),(4)
(6)
600
150
(3),(4)
(3),(4)
200
2000
(3),(4)
250
(3),(4)
700
DEFAULT
NOTE
1
1
2
1